Sollatek Maxima 3PH UR 10-20 kVA Datasheet (September 2025 v2)
Original title Sollatek Maxima 3PH UR September 2025 v2, PDF pp.2–4
Sollatek
Sollatek Maxima 3PH UR is a 10-20 kVA double-conversion UPS: unity output power factor, 95-96 percent double-conversion and 98-99 percent ECO efficiency, 0 ms transfer, up to 3 units in parallel.
On this page
Overview
The document is the datasheet (September 2025, v2) for the Maxima 3PH UR series of 10, 15 and 20 kVA UPS from Sollatek. The series is true double conversion, DSP-controlled and has a wide input range; capacities are given as 10000 VA/10000 W, 15000 VA/15000 W and 20000 VA/20000 W, so the output power factor is 1.0. Parallel operation (up to 3 units) and CVCF mode give scalability; protections such as OVCD, fan lock and overload warnings are built in.
Efficiency: in double conversion 95 percent (10 kVA) and 96 percent (15 and 20 kVA); in ECO mode 98 percent (10 kVA), 98.8 percent (15 kVA) and 99 percent (20 kVA). The input voltage range is 160 to 300 V (273 to 520 V line-to-line) at 100 percent load, with load derating linearly to 50 percent between 100 and 160 V (173 to 273 V); frequency is 50/60 Hz with a 40 to 70 Hz range; input power factor is above 0.995; THDi is below 3 percent on linear and 5 percent on non-linear load. Output voltage is 220/230/240 V or 380/400/415 V with ±1 percent accuracy, THDv below 1 percent on linear and 5 percent on non-linear load and a 3:1 crest factor.
Transfer time is 0 ms (2 ms from ECO+ mode to inverter). Overload (line mode) is 100-105 percent continuous, 105-125 percent for 10 minutes, 125-150 percent for 1 minute and above 150 percent for 500 ms. CVCF mode is supported (derating to 60 percent load on single-phase in and out). Interface: colour touch LCD (optional dot matrix), 10 languages, USB 2.0 HID, RS232, one programmable dry input and output, EPO, an intelligent slot and optional network, Modbus, AS400 and WLAN modules, an RJ45 Ethernet port and WinPower software.
The document lists CE and IEC/EN 62040 as certification and C3 as the conducted and EMI class. The table does not give size and weight columns on this page; the 10 kVA B (with battery) variant is chosen from the product code list.
Key points
- 10, 15 and 20 kVA; kVA = kW (output power factor 1.0).
- Double-conversion efficiency 95/96/96 percent; ECO mode 98/98.8/99 percent.
- Input range 160 to 300 V (273 to 520 V line-to-line) at 100 percent load; load derates linearly to 50 percent between 100 and 160 V.
- Input power factor above 0.995; THDi below 3 percent (linear) and 5 percent (non-linear).
- Output accuracy ±1 percent; THDv below 1 percent (linear) and 5 percent (non-linear); crest factor 3:1.
- Transfer time 0 ms (2 ms from ECO+ mode to inverter).
- Overload: 100-105 percent continuous, 10 min at 105-125 percent, 1 min at 125-150 percent, 500 ms above 150 percent.
- Up to 3 units in parallel (optional); CVCF mode; CE, IEC/EN 62040, EMI C3.
Using it in design
- With an output power factor of 1.0, the 20 kVA model delivers 20 kW; compare the load in kW with the rating.
- Compare the load dependence of the input window (50 percent load at 100 to 160 V) with battery use on a weak supply.
- Weigh the 98 to 99 percent ECO-mode efficiency and the 2 ms ECO+ to inverter transfer against load tolerance.
- Put the parallel capacity (up to 3 units) and the CVCF mode derating (60 percent) into the redundancy design.
- List the communication modules (network, Modbus, AS400, WLAN) in the specification according to monitoring needs.
Who should read it
Electrical designers and specification engineers selecting three-phase UPS for data-centre and critical facilities.
Document contents
- Description and features
- Technical specification: capacity, efficiency, input, output, general
- Interface and communication
- Certification and EMI
- Product code selection
Publication details
- Authors
- Sollatek
- Publisher
- Sollatek
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Sollatek Sollatek Maxima 3PH UR September 2025 v2, PDF pp.2–4. Sollatek. https://www.sollatek.com/wp-content/uploads/2025/02/Maxima-3PH-UR-10-20kVA-Datasheet-10911068-Sep-2025-v2-1.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.