Sollatek Maxima 3PH A3R 30-80 kVA Datasheet (June 2026 v2.1)

Original title Sollatek Maxima 3PH A3R June 2026 v2.1, PDF pp.2,6

Sollatek

Sollatek Maxima 3PH A3R is a 30-80 kVA VFI-SS-11 class double-conversion UPS: unity output power factor (kVA = kW), 96 percent online and up to 99 percent ECO efficiency, footprint cut by up to 50 percent.

On this page

Overview

The document is the datasheet (June 2026, v2.1) for the Maxima 3PH A3R series of 30, 40, 60 and 80 kVA three-phase UPS from Sollatek. The series is double conversion with IGBT converters and IEC 62040-3 class VFI-SS-11. With an output power factor of 1.0, capacities are 30/30, 40/40, 60/60 and 80/80 kVA/kW. With three-step IGBT PWM control, online-mode efficiency reaches up to 96 percent and ECO-mode efficiency up to 99 percent; the higher-density design cuts the footprint by up to 50 percent.

Battery management stands out: Optimised Battery Management (OBM) technology extends battery life by up to 50 percent (typical profile 90 percent resting, 10 percent floating/charging), with an adjustable 32 to 44 battery configuration, a powerful charger and support for up to 4 external battery modules (EBMs) to extend backup time (batteries not included). The user interface is a 5-inch colour touchscreen in 10 languages; PCBA conformal coating and a dust filter are fitted.

Input: 230/400 V nominal; rectifier tolerance -15/+20 percent at 100 percent load and -50/-15 percent at 50 percent load; frequency 50 or 60 Hz with 40 to 72 Hz tolerance; THDi below 3 percent and input power factor of 0.99 at 100 percent load. Output voltage is ±1 percent on balanced and ±2 percent on unbalanced load. Overload without bypass is 105-110 percent for 60 minutes, 111-125 percent for 10 minutes, 126-150 percent for 1 minute and above 150 percent for 150 seconds. Double-conversion efficiency is about 93.2 to 96.0 percent from 25 to 100 percent load and 98.8 to 99.2 percent in ECO mode.

Physical values: weight without batteries is 136, 139, 239 and 242 kg and with batteries 309, 346, 530 and 630 kg; dimensions are 500 × 859 × 887 mm (30-40 kVA) and 500 × 846 × 1500 mm (60-80 kVA); protection is IP20; noise at 1 m and 75 percent load is at most 65 dBA; service temperature is 0 to 40 °C for the power electronics (40 to 50 °C with derating) and 5 to 25 °C for the battery; altitude is derating-free to 1000 m, then 1 percent per additional 100 m up to 2000 m. Communication: two intelligent slots, an EPO input, 3 building alarms, RS-232 and USB (service); optional NMC G2, CMC G2 and relay cards.

Key points

  1. 30, 40, 60 and 80 kVA; kVA = kW (output power factor 1.0); class VFI-SS-11.
  2. Efficiency up to 96 percent online and up to 99 percent in ECO mode; double-conversion efficiency about 93.2 to 96.0 percent from 25 to 100 percent load.
  3. Footprint cut by up to 50 percent; size 500 × 859 × 887 mm (30-40 kVA), 500 × 846 × 1500 mm (60-80 kVA).
  4. OBM technology extends battery life by up to 50 percent; 32 to 44 batteries adjustable.
  5. Input THDi below 3 percent, input power factor 0.99 (100 percent load); input frequency 40 to 72 Hz.
  6. Output voltage ±1 percent on balanced and ±2 percent on unbalanced load.
  7. Overload (without bypass): 105-110 percent for 60 min, 111-125 percent for 10 min, 126-150 percent for 1 min, above 150 percent for 150 s (40 °C).
  8. Weight without batteries 136 to 242 kg, with batteries 309 to 630 kg; noise at most 65 dBA; IP20.

Using it in design

  • With an output power factor of 1.0, compare the load in kW directly with the rating (kVA = kW).
  • Reflect the battery bank (32 to 44 batteries) and OBM's rest-heavy charge profile in battery life and the replacement plan.
  • Calculate floor loading from the weight with batteries (309 to 630 kg).
  • Use the input current values (rectifier 45 to 122 A, bypass 44 to 118 A at 400 V) in cable and protection sizing.
  • Weigh the 98.8 to 99.2 percent ECO-mode efficiency against load class and transfer behaviour.

Who should read it

Electrical designers and specification engineers selecting three-phase UPS for data-centre and critical facilities.

Document contents

  1. Description and features
  2. Technical specification: model, classification, size and weight, environment
  3. User interface and communication
  4. Input
  5. Output: double conversion
  6. Efficiency
  7. Bypass, battery and overload

Publication details

Authors
Sollatek
Publisher
Sollatek
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Sollatek Sollatek Maxima 3PH A3R June 2026 v2.1, PDF pp.2,6. Sollatek. https://www.sollatek.com/wp-content/uploads/2025/02/Maxima-3PH-A3R-30-80kVA-Datasheet-10911069-Jun-2026-v2.1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.