Sollatek Ultima S Series 650-2200 VA UPS Datasheet

Original title Sollatek Ultima S March 2024 v3, PDF pp.2,4

Sollatek

Sollatek's March 2024 datasheet defines the five-model Ultima S line-interactive range from 650 to 2200 VA, with a 170-280 VAC input window, 2-8 ms transfer time and a stepped sine output.

On this page

Overview

The document gives the UK manufacturer Sollatek's Ultima LCD 650, 850, 1200, 1500 and 2200 VA models in a single table. They are microprocessor-controlled line-interactive UPSs aimed at small loads such as computers, network, security and telecom equipment. Capacities run from 360 W to 1200 W, and the output power factor varies between 0.5 and 0.6 by model.

Input is 230 VAC nominal and accepts 170-280 VAC. In battery mode the output voltage is held to +/-10% and frequency to +/-1 Hz, with a stepped sine waveform. Transfer time is typically 2-6 ms on the smaller models and 4-8 ms on the larger ones. Automatic voltage regulation (AVR), DC cold start, USB-HID communication and RJ11/RJ45 line protection are listed as standard.

The battery side uses 12 V lead-acid blocks of 7 Ah and 9 Ah: one block on the small models, two from 1200 VA upward. Recharge to 90% takes 4 hours after full discharge. Estimated backup at a 100 W load is 16, 20, 40, 40 and 50 minutes. The sheet labels the product category C2 and notes it may cause radio interference in a residential environment.

The document does not present a replacement for a data-centre double-conversion UPS. Data centres are named among the applications, but power, battery and runtime figures are at the scale of edge loads, network cabinets and surveillance equipment. Weights and dimensions are approximate.

Key points

  1. Five models: 650 VA/360 W, 850 VA/480 W, 1200 VA/600 W, 1500 VA/900 W, 2200 VA/1200 W.
  2. Output power factor is 0.55, 0.56, 0.5, 0.6 and 0.55, so the VA rating alone does not give real power.
  3. Input is 230 VAC with a 170-280 VAC operating range; in battery mode the output is +/-10% and +/-1 Hz.
  4. Transfer time is typically 2-6 ms (small models) and 4-8 ms (large models); output is a stepped sine wave.
  5. Battery: 12 V/7 Ah x1, 12 V/9 Ah x1, 12 V/7 Ah x2 (two models) and 12 V/9 Ah x2.
  6. Estimated backup at 100 W is 16, 20, 40, 40 and 50 minutes; recharge to 90% in 4 hours.
  7. Operating temperature is 0-40 C; noise is 40 dB (small) and 45 dB (large models).
  8. Weights are 4.4, 5.2, 7.85, 9.4 and 10.4 kg; dimensions are given for two enclosures, 290 x 100 x 143 mm and 364 x 139 x 195 mm.

Using it in design

  • A stepped sine output can upset server power supplies with active PFC; confirm load compatibility with the manufacturer.
  • When selecting, compare the W rating against the load rather than VA: the 1200 VA model delivers 600 W and the 2200 VA model 1200 W.
  • Runtime is quoted for a 100 W load; scale it for the real load and check adequacy separately for edge points such as network cabinets.
  • Critical white-space load needs a double-conversion class; this series suits small auxiliary loads only.
  • Confirm the socket type (Euro or UK) separately in the order code, since the product code distinguishes them.

Who should read it

Electrical designers selecting a UPS for small loads and edge protection, and network and security infrastructure owners.

Document contents

  1. Description
  2. Features and protection
  3. Technical specification table
  4. LCD panel
  5. Rear panel
  6. Product code description

Publication details

Authors
Sollatek
Publisher
Sollatek
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Sollatek Sollatek Ultima S March 2024 v3, PDF pp.2,4. Sollatek. https://www.sollatek.com/wp-content/uploads/2024/03/Ultima-S-Series-650-2200VA-Datasheet-10911005-Mar-2024-v3.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.