Qoltec 53984 official technical data: 3-phase UPS 15kVA / 12kW high frequency
Original title Qoltec 53984 official technical data
Qoltec
The Qoltec 53984 is a 15 kVA / 12 kW three-phase high-frequency online UPS with 400 V (3Ph+N) rating, 0 ms transfer time, built-in SNMP module, delivery without batteries and 37.53 kg weight.
On this page
Overview
The page presents Qoltec's three-phase high-frequency online UPS, product code 53984. The unit is rated 15 kVA apparent and 12 kW active power, provides pure sine output, and its rated voltage is written as 400 V AC (3Ph+N). Three-phase input voltage is 190-520 V AC at 50 percent load and 305-478 V AC at 100 percent load. In battery mode the output is 3 x 380 V AC (3Ph+N) ± 1 percent at 50/60 Hz ± 0.05 Hz.
Transfer time is 0 ms and crest factor is 3:1; on overload the unit switches to bypass within 4 ms. Protections cover over voltage, overload, short circuit, high and low voltage and over temperature. The battery block voltage is 12 V. Charging time in the standard type is 8 hours to 90 percent of battery capacity. The unit is delivered without batteries; the battery set is built from 12 V blocks.
Communication is provided through USB, RS-232 and a built-in SNMP module; an LCD and an EPO input are also fitted. Noise is below 60 dB. Operating temperature is 0 to +40 °C, storage temperature is -15 to +60 °C and relative humidity is 20-95 percent. The package contains the UPS, USB-B cable, power cable, user manual, SNMP manual, ViewPowerPro software and warranty card.
Dimensions are 570 x 250 x 540 mm (D x W x H), net weight 37.53 kg and gross weight 40.52 kg. The unit is CE and RoHS certified with a 24-month warranty. The page gives no runtime value; runtime depends on the battery capacity chosen.
Key points
- Model 53984; 15 kVA / 12 kW; three-phase pure sine; high-frequency online.
- Rated voltage 400 V AC (3Ph+N); input 190-520 V AC (50 percent load) and 305-478 V AC (100 percent load).
- Battery-mode output 3 x 380 V AC ± 1 percent; 50/60 Hz ± 0.05 Hz.
- Transfer time 0 ms; bypass within 4 ms on overload; crest factor 3:1.
- The battery block voltage is 12 V.
- Standard-type charging time: 8 hours to 90 percent of capacity.
- USB, RS-232, built-in SNMP; EPO; LCD; noise below 60 dB.
- 570 x 250 x 540 mm; net 37.53 kg; 0 to +40 °C; CE, RoHS; 24-month warranty.
Using it in design
- In the distribution design, check the three-phase connection with neutral (3Ph+N) and the load-dependent input voltage range.
- Select battery capacity for runtime; the unit ships without batteries and the page gives no runtime.
- Connect the built-in SNMP module to the building monitoring system and add the EPO input to the emergency shutdown circuit.
- Assess noise (below 60 dB) and weight in the room layout.
Who should read it
Technical-room and small data-centre designers selecting mid-range three-phase UPS units.
Document contents
- Product description
- Technical data
- Other parameters
- Package contents
Publication details
- Authors
- Qoltec
- Publisher
- Qoltec
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Qoltec Qoltec 53984 official technical data. Qoltec. https://www.qoltec.com/product/duplicate-qoltec-3-phase-ups-10kva-8kw-lcd-epo-usb-on-line
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.