Qoltec 53938 official technical data: RACK pure sine UPS 3 kVA / 3000 W

Original title Qoltec 53938 official technical data

Qoltec

The Qoltec 53938 is a 3 kVA / 3000 W (power factor 1.0) rack pure sine double-conversion online UPS with a 48 V DC battery set, LiFePO4, AGM and GEL compatibility, 0 ms transfer time and 10.56 kg weight.

On this page

Overview

The page presents Qoltec's rack-mount UPS, product code 53938. The unit is rated 3 kVA apparent and 3000 W active power; because the power factor is 1.0, the full apparent power can be used as active power. The double-conversion online design gives pure sine output with constant output voltage and frequency. The manufacturer names server rooms, data centres, ICT systems and large network installations as intended use.

Input voltage is 110-300 V AC ± 5 percent; the voltage range is written as 110-160 V AC at 50 percent load and 160-300 V AC at 100 percent load (± 3 percent). Output is 230 V AC and frequency 50/60 Hz ± 0.05 Hz. Transfer time is 0 ms between AC and battery mode, 4 ms between inverter and bypass, and 8 ms between ECO mode and battery mode. On overload the unit switches to bypass after 4 ms. Crest factor is 3:1.

The battery system is not included; lithium or lead-acid batteries can be used and the battery set voltage is 48 V DC. Charging current is adjustable from 10 A to 60 A, with 90 percent of capacity reached in 1.5 hours. Features include True Isolation technology, a built-in service bypass, an EPO interface, RS-232 and USB-B ports, two fans, an LCD, management through an SNMP manager and the ability to connect several UPS units in parallel. Noise is below 50 dB, operating temperature is 0 to +55 °C and relative humidity is 20-95 percent.

Physical data: dimensions 420 x 440 x 88 mm (D x W x H), net weight 10.56 kg, gross weight 12.07 kg, CE and RoHS certification and a 24-month warranty. Since the unit is supplied without batteries, runtime depends on the chosen battery capacity; the page gives no minute values.

Key points

  1. Model 53938; 3 kVA / 3000 W; power factor 1.0; pure sine; double-conversion online.
  2. Input 110-300 V AC ± 5 percent; output 230 V AC; frequency 50/60 Hz ± 0.05 Hz.
  3. Transfer time: AC/battery 0 ms; inverter/bypass 4 ms; ECO mode/battery 8 ms.
  4. Batteries not included; 48 V DC battery set; lithium or lead-acid compatible.
  5. Charging current adjustable 10-60 A; 90 percent of capacity in 1.5 hours.
  6. On overload, bypass after 4 ms; crest factor 3:1.
  7. 420 x 440 x 88 mm; net 10.56 kg; noise below 50 dB; 0 to +55 °C.
  8. EPO, RS-232, USB-B and SNMP management; parallel connection possible; 24-month warranty.

Using it in design

  • For the 48 V DC battery set, choose the series cell count and battery type (LiFePO4, AGM or GEL) and set the charging current to the battery manufacturer's limit.
  • Calculate runtime separately from battery capacity and load; the unit contains no batteries.
  • For parallel operation, check the cabling and setting conditions in the manufacturer's manual.
  • Wire the EPO input into the facility emergency shutdown circuit and plan monitoring through the SNMP manager.
  • Include the 10.56 kg weight and 88 mm height (2U class) in the rack load plan.

Who should read it

Designers selecting 3 kVA class online UPS units for server rooms and network racks.

Document contents

  1. Product description
  2. Full description
  3. Pure sine wave
  4. Backup time
  5. LCD display
  6. Warranty
  7. Technical data
  8. Other parameters

Publication details

Authors
Qoltec
Publisher
Qoltec
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Qoltec Qoltec 53938 official technical data. Qoltec. https://qoltec.com/product/qoltec-uninterruptible-power-supply-ups-for-rack-3kva-3000w-power-factor-10-lcd-epo-usb-on-line

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.