Qoltec 53947 official technical data: UPS RACK 3 kVA / 2400 W LCD
Original title Qoltec 53947 official technical data
Qoltec
The Qoltec 53947 is a 3 kVA / 2400 W rack online UPS with pure sine output, built-in 6 x 12 V 7 Ah batteries (72 V), 26 minutes of backup at 500 W and 22.2 kg weight.
On this page
Overview
The page presents Qoltec's UPS, product code 53947, designed for mounting in rack cabinets. The unit is rated 3 kVA apparent and 2400 W active power, with a power factor of 0.8. Pure sine output, zero switching time, double conversion and True Isolation technology protect sensitive devices against mains fluctuations. Recommended use is computers, servers, alarm systems and routers, as well as industrial and manufacturing environments and medical centres.
Input voltage is 115-300 V AC ± 5, output voltage is 220 V AC ± 1 percent, input frequency range is 45-55 Hz ± 0.5 Hz and output frequency is 50 Hz ± 1 percent (46-54 Hz). In bypass mode the output voltage ranges from 80 to 285 V AC. On overload between 105 and 125 percent the unit switches to bypass after 1 minute. The unit carries 6 internal 12 V 7 Ah batteries and the battery set voltage is 72 V.
The runtime table depends on load: 133 minutes at 100 W, 66 minutes at 200 W, 44 minutes at 300 W, 26 minutes at 500 W and 13 minutes at 1000 W. Features include ECO mode, an extended runtime option, a built-in service bypass, an RS-232 port and cable, two fans, an LCD, and a compatible SNMP module with product code 50386. Output sockets are 2 x SCHUKO and 1 x IEC; noise is below 50 dB.
Physical data: dimensions 635 x 483 x 87 mm (D x W x H), net weight 22.2 kg, gross weight 22.9 kg, operating temperature 0 to +40 °C, CE and RoHS certification and a 24-month warranty.
Key points
- Model 53947; 3 kVA / 2400 W; power factor 0.8; pure sine; online double conversion.
- Input 115-300 V AC ± 5; output 220 V AC ± 1 percent; output frequency 50 Hz ± 1 percent.
- Built-in batteries: 6 x 12 V 7 Ah; battery set 72 V.
- Runtime: 100 W 133 min; 200 W 66 min; 300 W 44 min; 500 W 26 min; 1000 W 13 min.
- Overload of 105-125 percent switches to bypass after 1 minute; bypass output range 80-285 V AC.
- Sockets: 2 x SCHUKO, 1 x IEC; RS-232; SNMP module (code 50386).
- 635 x 483 x 87 mm; net 22.2 kg; noise below 50 dB; 0 to +40 °C.
- CE, RoHS; 24-month warranty.
Using it in design
- Keep the load below 2400 W and compare the load list's power factor with the 0.8 limit.
- Use the runtime table against the real load; for example 26 minutes at 500 W.
- Include the 22.2 kg weight and 635 mm depth in the rack load and depth plan.
- Add the SNMP module with code 50386 to the order scope for remote monitoring.
- Confirm the extended runtime option with the manufacturer if long backup is required.
Who should read it
Designers selecting 3 kVA class online UPS units for small server rooms and network racks.
Document contents
- Product description
- Full description
- Pure sine wave
- How an online UPS works
- LCD display
- Warranty
- Technical data
- Backup time table
Publication details
- Authors
- Qoltec
- Publisher
- Qoltec
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Qoltec Qoltec 53947 official technical data. Qoltec. https://qoltec.com/product/qoltec-uninterruptible-power-supply-ups-rack-3kva-2400-w-lcd
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.