Data Center and Cloud Services Directives (Rwanda)
Original title Data Center and Cloud Services Directives
Rwanda Information Society Authority
Rwanda Information Society Authority (RISA) guidelines cover data-centre design process, site selection, space planning, architectural and structural design, electrical systems and security; floor loading of at least 7.2 kPa is required.
On this page
Overview
RISA's online technical guide collects the factors to consider when setting up and managing a data centre. The design-process page calls for coordinated cabling, electrical, architectural, HVAC, security and lighting plans. The guide also covers cloud service and deployment models, organisation and human resources, security, and business continuity and disaster recovery.
The facility sections are site selection and evaluation, space planning, architectural and structural design, and power and electrical systems. The architectural section includes the computer room, entrance rooms (separate for class 3 and above), mechanical room, electrical and UPS room, a separate fire suppression room for class 4, equipment staging and storage, floor slab, wall and fire-rated construction, access control and equipment bracing. Superimposed floor loading is stated as at least 7.2 kPa (150 lbf/ft2). The electrical section covers transformers, generators, redundancy, five electrical classes, UPS, PDUs, DC systems, monitoring and grounding.
On the operations side, 24/7 operation, security personnel inside Tier 3 and Tier 4 facilities, restoration tests and public-power-to-UPS failover testing appear in the operating and recovery lists.
Key points
- The design process asks for coordinated cabling, electrical, architectural, HVAC, security and lighting plans.
- Tier 3 and Tier 4 data centres should have security personnel inside the facility.
- Class 3 and higher facilities have separate entrance rooms, and class 4 a separate fire suppression room.
- Floor loading (superimposed live load) must be at least 7.2 kPa (150 lbf/ft2).
- The electrical section covers five electrical classes, UPS, PDUs, DC systems and grounding.
- Operating lists include restoration tests and public-power-to-UPS failover testing.
Using it in design
- Merge the discipline plans (electrical, architectural, HVAC, cabling, security) into one coordination matrix.
- Set early in design the separate entrance room, electrical and UPS room and fire suppression room needs for the target class.
- Check structural design for superimposed floor loading of at least 7.2 kPa.
- Add public-power-to-UPS failover and restoration tests to the commissioning acceptance list.
Who should read it
Engineers designing and operating data centres in Rwanda, public bodies and compliance teams.
Publication details
- Authors
- Rwanda Information Society Authority
- Publisher
- Rwanda Information Society Authority
- Year
- Year not stated
- Document language
- English
- Source type
- Government / public
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public official source inspected; no document-specific commercial redistribution permission established. Original short summaries and metadata only; downloads are local research evidence.
Citation
Rwanda Information Society Authority Data Center and Cloud Services Directives. Rwanda Information Society Authority. https://guidelines.risa.gov.rw/books/data-center-and-cloud-services-directives
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.