Advisory Guidelines for Resilience and Security of Data Centres (Singapore IMDA, 2025)
Original title Advisory Guidelines for Resilience and Security of Data Centres
Infocomm Media Development Authority
Singapore IMDA's 7-page voluntary guideline of 25 February 2025 groups data centre risk into infrastructure, governance and cyber, and recommends a Plan-Do-Check-Act business continuity management system (BCMS).
On this page
Overview
The Infocomm Media Development Authority (IMDA) guideline gives best practices for the resilience and security of Singapore's compute infrastructure such as cloud and data centres. It is for voluntary adoption; the issuing authority encourages data centres to adopt it to strengthen their own security posture and stand out in the market. The introduction notes that Singapore's digital economy was about 17.7% of GDP in 2023.
The risk section defines three areas. Infrastructure risks cover power management (inadequate power redundancy during maintenance, inadequate lightning protection), environmental control (cooling redundancy), cable management (insufficient bend radius), facility and tenant space protection (unauthorised access, fire detection and suppression) and site and design suitability (flooding and water intrusion). Governance risks are operations, incident and change management. Under cyber risk, an example is a DCIM system being compromised and temperature changed without authorisation.
The management approach rests on the Plan, Do, Check, Act loop. Plan sets policy, scope (critical services such as power, cooling and connectivity) and top management support, and the system is updated when new products such as lithium-ion batteries are introduced. Do covers business impact analysis, risk assessment, redundant power, lightning protection, fire detection and ransomware measures, response plans and regular exercises. The guideline refers to ISO 22301, ISO 27001/2, ISO 31000, ISO 22237 and TIA-942.
The document is a high-level management and risk guideline; it gives no numerical design values, redundancy topology or measurable targets. The last section lists further cyber measures: an information security management system, personnel and third-party controls, audit trails, secure configuration, patch management, open-source component safety, vulnerability scans and penetration tests.
Key points
- The guideline is dated 25 February 2025, is for voluntary adoption and will be updated regularly.
- Three main risk areas: infrastructure, governance and cybersecurity.
- One infrastructure risk is power outage from inadequate power redundancy during planned maintenance or inadequate lightning protection.
- Inadequate cooling redundancy, insufficient cable bend radius and water intrusion from flooding are listed as separate risk items.
- Where primary monitoring is unavailable during planned maintenance, alternative monitoring must be put in place so alarms are not masked.
- No unplanned change may run in parallel with an approved change, and deviations must be approved by the change advisory board.
- The BCMS is built on the Plan, Do, Check, Act loop; business impact analysis sets the maximum tolerable disruption time.
- Reference standards: ISO 22301, ISO 27001/2, ISO 31000, ISO 22237 and TIA-942.
- Cyber measures include audit trails, patch management, open-source component checks, vulnerability scans and penetration tests.
Using it in design
- Add separate lines to the design risk register for power and cooling redundancy during maintenance, lightning protection, cable bend radius and flood protection.
- In the monitoring architecture, design a second monitoring path that takes over when the primary monitoring system is down for planned maintenance.
- Use the maximum tolerable disruption time from the business impact analysis as an input to Tier and redundancy level selection.
- When introducing new technology such as lithium-ion batteries, update the continuity plan and the change management record.
- Bring the DCIM and BMS network into OT cybersecurity scope and test scenarios such as unauthorised temperature setpoint changes.
Who should read it
Data centre operators, risk and continuity managers, and designers serving the Singapore market.
Document contents
- Introduction
- Key risks for the resilience and security of DCs
- Managing resilience and security risks of DCs
- Additional measures to manage cyber risks
Publication details
- Authors
- Infocomm Media Development Authority
- Publisher
- Infocomm Media Development Authority
- Year
- 2025
- Document language
- English
- Source type
- Government / public
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public publisher source inspected. No document-specific commercial redistribution permission established; metadata and original short summaries only. Local downloads are research evidence, not a redistribution package.
Citation
Infocomm Media Development Authority (2025). Advisory Guidelines for Resilience and Security of Data Centres. Infocomm Media Development Authority. https://www.imda.gov.sg/-/media/imda/files/regulations-and-licensing/regulations/codes-of-practice/codes-of-practice-dco-and-csp/ag-for-resilience-and-security-of-data-centres.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.