Technical guideFree to read2024

Study on the Characterization of Filters for a Direct-to-Chip Liquid Cooling System (40th SEMI-THERM Symposium, 2024)

SEMI-THERM · Pardeep Shahi, Ali Heydari et al.

An experimental study measuring the effect of strainer filters of different mesh sizes in the secondary loop of a direct-to-chip system on pressure drop and flow.

On this page

Overview

This paper is an experimental study presented at the 40th SEMI-THERM Symposium in 2024. Its authors include Pardeep Shahi, Ali Heydari, Dereje Agonafer and Mohammad Tradat. The study starts from the premise that filtration in the coolant distribution unit (CDU) is key to protecting cold-plate microchannels from particulates.

The experiments were carried out on strainer filters in the secondary loop of a direct-to-chip system. Using a CDU and rack, filters of 25, 50 and 100 micron mesh were compared with the no-filter case; CDU pump speed was varied between 20% and 100% by a variable frequency drive, with the coolant held at 32 C. The authors measured pressure drop across the filters, the resulting loop flow, and filter condition over time.

According to the results, the pressure-drop difference between no filter and the 25 micron filter grew from about 0.11 psi at 20% pump speed to about 0.64 psi at 100%. At maximum pump speed loop flow was about 390 L/min, and flow differences between filter cases were around 1% or less. With 100 and 50 micron filters at 80% speed, flow was 308-309 L/min, and the 25 micron filter gave the highest pressure loss. These findings show that finer mesh adds a measurable but small hydraulic penalty.

As a limit, the results are confined to the flows tested, a single CDU and rack arrangement; behaviour may change with a different coolant, contamination load or long-term clogging. Even so, the study offers a measured reference for how filter micron rating can enter the hydraulic calculation, and it should be read alongside the OCP Cold Plate Cooling Loop Requirements.

Key points

  1. Filters of 25, 50 and 100 micron mesh compared with no filter at CDU pump speeds of 20-100% (VFD), coolant held at 32 C.
  2. Pressure-drop difference between no filter and the 25 micron filter grew from about 0.11 psi at 20% pump speed to about 0.64 psi at 100%.
  3. At maximum pump speed loop flow was about 390 L/min; flow differences between filter cases were around 1% or less.
  4. With 100 and 50 micron filters at 80% speed, flow was 308-309 L/min; the 25 micron filter gave the highest pressure loss.
  5. Filtration in the CDU is presented as key to protecting cold-plate microchannels from particulates.
  6. Finer mesh adds a measurable but small pressure drop and flow penalty.

Using it in design

  • Include the filter micron rating and its pressure-drop curve in the hydraulic calculation for CDU and loop objects.
  • Default to finer filtration (25 micron) for microchannel cold plates, since its hydraulic penalty is small.
  • Add monitoring of filter condition over time to the maintenance plan.
  • Account for the pressure-drop difference growing with pump speed when selecting pumps.

Who should read it

Engineers designing CDUs, filters and secondary-loop hydraulics for direct-to-chip liquid-cooled systems.

Related standards

  • OCP Cold Plate Cooling Loop Requirements

Publication details

Authors
Pardeep Shahi; Ali Heydari; Himanshu Modi; Lochan Sai Reddy Chinthaparthy; Anto Barigala; Qusai Soud; Uschas Chowdhury; Dereje Agonafer; Mohammad Tradat; Jeremy Rodriguez
Publisher
SEMI-THERM
Year
2024
Document number
40th SEMI-THERM Symposium; NSF PAR 10537801
Event
40th SEMI-THERM Symposium (2024)
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Pardeep Shahi; Ali Heydari; Himanshu Modi; Lochan Sai Reddy Chinthaparthy; Anto Barigala; Qusai Soud; Uschas Chowdhury; Dereje Agonafer; Mohammad Tradat; Jeremy Rodriguez (2024). Study on the Characterization of Filters for a Direct-to-Chip Liquid Cooling System (40th SEMI-THERM Symposium, 2024). SEMI-THERM. 40th SEMI-THERM Symposium; NSF PAR 10537801. 40th SEMI-THERM Symposium (2024). https://par.nsf.gov/servlets/purl/10537801

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.