Shenglin CMC Series Chilled Water Fan Wall Unit

Original title CMC chilled water fan wall: technical specification

Shenglin

Shanghai Shenglin M&E's CMC chilled-water fan wall: 210 kW total and sensible capacity, 60,000 m³/h horizontal airflow, EER of 10 or more, rated at 20/28°C water and 36°C return air.

On this page

Overview

The product page introduces the CMC series chilled-water fan wall from Shenglin's Cyber-Master range of large computer room air conditioners. The unit normally forms a cooling system with chillers, pumps and chilled-water piping and gives precise temperature and humidity control. The maker states that types not listed can be customised on request.

The specification table gives a single model: 210 kW total and sensible capacity, horizontal air supply, 60,000 m³/h airflow, 0-300 Pa external static pressure, EER of at least 10, 24 kW reheat, 10 kg/h humidification, G4 filter and 2,200 x 2,000 x 1,200 mm (H x W x D). The capacity condition is stated explicitly: 20/28°C water, 36°C and 24% RH return air, 24°C (±1°C) supply air and 100 Pa external static pressure.

The reference examples on the page belong to the maker's other precision air conditioners, not the fan wall (for instance a 36.7 kW DX unit, a hospital MRI room and a wind farm). The only fan wall data point is therefore the 210 kW model and its stated condition. The references show the range of uses of the product family (data centre, hospital, base station, wind farm).

Key points

  1. Total and sensible cooling capacity of 210 kW (sensible ratio 1.0).
  2. Airflow 60,000 m³/h, horizontal air supply, external static pressure 0-300 Pa.
  3. EER at least 10; refrigerant type is chilled water.
  4. Rating condition: water 20/28°C, return air 36°C dry bulb and 24% RH, supply air 24°C ±1°C, ESP 100 Pa.
  5. Reheat 24 kW, humidification 10 kg/h, filter class G4.
  6. Dimensions 2,200 x 2,000 x 1,200 mm (H x W x D).

Using it in design

  • Use the 210 kW figure only at 20/28°C water and 36°C return air; if your water temperatures differ, ask the manufacturer for corrected capacity.
  • Compare the 60,000 m³/h airflow against the rack airflow demand of the enclosed aisle and the 100 Pa ESP.
  • Check the 8 K water delta-T against your chiller and pump design.
  • Add reheat and humidification to the electrical load calculation.

Who should read it

Mechanical designers selecting chilled-water fan wall CRAH units.

Document contents

  1. Features
  2. Technical data
  3. Application
  4. Certification
  5. Part list
  6. Reference

Publication details

Authors
Shenglin
Publisher
Shenglin
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Shenglin CMC chilled water fan wall: technical specification. Shenglin. https://shenglin-tech.com/products/Chilled_Water_Fan_Wall_Unit/1549.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.