Shenglin CRCX and CRCX-E DX in-row units, modulation data
Original title Shenglin CRCX / CRCX-E direct-expansion in-row cooling
Shenglin
Shenglin's CRCX direct-expansion in-row series modulates across three models, with maximum 11.84, 18.71 and 33.02 kW and minimum 5.64, 8.19 and 14.09 kW capacity.
On this page
Overview
The page presents Shanghai Shenglin M&E Technology's CRCX direct-expansion in-row unit and its closed-system (CRCX-E) variant. Advantages: flexible modular design, ease of data-centre expansion, fit for 42U and 48U cabinets, a minimum footprint of 0.3 m², cold air only where needed, plug-and-play installation, power and cooling backup and EC fan maintenance without interrupting operation.
In the table the models are 0051, 0071 and 0121. Maximum and minimum total capacity equal sensible capacity: 11.84 / 5.64 kW, 18.71 / 8.19 kW and 33.02 / 14.09 kW. Compressor power is 2.66, 4.65 and 7.40 kW at maximum and 0.73, 1.15 and 1.81 kW at minimum. Air flow is 1,500, 2,700 and 4,200 m³/h at maximum and 900, 1,200 and 1,800 m³/h at minimum.
EER is 3.8, 3.5 and 3.9 at maximum and 5.2, 4.9 and 5.0 at minimum (efficiency rises at part load). Supply is 230 V single phase 50 Hz for 0051 and 400 V three phase 50 Hz for 0071 and 0121. Liquid line is 12, 16 and 18 mm and gas line 18, 22 and 28 mm. The indoor unit is 2,050 x 1,190 x 300 mm, 200-217.5 kg; outdoor units are 1,240 x 420 x 900, 1,470 x 570 x 1,700 and 1,700 x 570 x 1,700 mm.
Key points
- Three models: maximum / minimum total and sensible capacity 11.84 / 5.64, 18.71 / 8.19 and 33.02 / 14.09 kW (0051 / 0071 / 0121).
- Compressor power 2.66 / 4.65 / 7.40 kW maximum, 0.73 / 1.15 / 1.81 kW minimum.
- Air flow 1,500 / 2,700 / 4,200 m³/h maximum, 900 / 1,200 / 1,800 m³/h minimum.
- EER 3.8 / 3.5 / 3.9 at maximum; 5.2 / 4.9 / 5.0 at minimum load.
- Supply: 230 V single phase for 0051, 400 V three phase for 0071 and 0121, 50 Hz.
- Refrigerant lines: liquid 12 / 16 / 18 mm, gas 18 / 22 / 28 mm.
- Indoor unit 2,050 x 1,190 x 300 mm, 200-217.5 kg; outdoor units 900-1,700 mm wide.
Using it in design
- Where rack load varies, check the minimum capacity (5.64-14.09 kW); the modulation range sets cycling frequency at low load.
- Plan the outdoor unit position, size and liquid-gas line length early.
- The table does not state the ambient conditions behind the capacity values; confirm with the manufacturer before ordering.
- Model 0051 is single phase and the others three phase, so plan supply per model.
Who should read it
Mechanical and electrical engineers designing DX in-row cooling.
Document contents
- Advantages
- CRCX direct-expansion series and CRCX-E closed series technical data table
- Applications
Publication details
- Authors
- Shenglin
- Publisher
- Shenglin
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Shenglin Shenglin CRCX / CRCX-E direct-expansion in-row cooling. Shenglin. https://shenglin-tech.com/Precision%20AC/In_row_Cooling/654.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.