Shenglin CRCC and CRCC-E chilled-water in-row tables

Original title Shenglin CRCC / CRCC-E chilled-water in-row cooling

Shenglin

Shenglin's CRCC chilled-water in-row series suits 42U/48U cabinets at 300 mm wide, with four models giving 20.44-31.25 kW of total and sensible capacity.

On this page

Overview

The page presents Shanghai Shenglin M&E Technology's CRCC chilled-water in-row unit and its closed-system (CRCC-E) variant. Advantages listed are efficient operation at small air volume, flexible modular design, optimised management of each server cabinet, fit for 42U and 48U cabinets, plug-and-play installation, power and cooling backup, EC fan maintenance without interrupting operation and optional humidification.

In the table the models are 0020, 0025, 0035 and 0036. Total capacity is 20.44, 26.06, 31.25 and 26.79 kW, equal to sensible capacity. Water pressure drop is 30, 40, 45 and 80 kPa, water flow 2.93, 3.74, 4.49 and 3.85 m³/h, evaporator fan power 0.516, 0.688, 0.860 and 0.860 kW and air flow 2,520, 3,360, 4,200 and 4,200 m³/h.

Supply is 230 V single phase 50 Hz for 0020 and 0025 and 240 V single phase 50 Hz for 0035 and 0036. Model 0036 has two circuits and the others one. The indoor unit is 2,050 x 1,190 x 300 mm (H x D x W) and weighs 215, 217.5, 220 and 230 kg. Application areas are communication rooms, computer centres, laboratories, hospital CT and MRI rooms and control and monitoring centres.

Key points

  1. Four models: total and sensible capacity 20.44 / 26.06 / 31.25 / 26.79 kW (0020 / 0025 / 0035 / 0036).
  2. Water flow 2.93 / 3.74 / 4.49 / 3.85 m³/h; water pressure drop 30 / 40 / 45 / 80 kPa.
  3. Air flow 2,520 / 3,360 / 4,200 / 4,200 m³/h; evaporator fan power 0.516-0.860 kW.
  4. Supply 230 V (0020, 0025) or 240 V (0035, 0036), single phase, 50 Hz.
  5. Model 0036 has two circuits, the others one.
  6. Indoor unit 2,050 x 1,190 x 300 mm; weight 215-230 kg.
  7. Suits 42U and 48U cabinets; the system keeps running during EC fan maintenance.

Using it in design

  • In row layouts, match kW per cabinet with the model's sensible capacity; carry model 0036's high 80 kPa pressure drop, against its lower capacity, into the pump calculation.
  • The table does not state the rating conditions (water and return air temperature); confirm capacity at the real regime with the manufacturer.
  • For single-phase supply (230/240 V), plan phase balance on the distribution board.
  • Carry the 300 mm module width and 1,190 mm depth into the row plan and service clearance.

Who should read it

Mechanical and electrical engineers designing in-row cooling.

Document contents

  1. Advantages
  2. CRCC chilled-water series and CRCC-E closed series technical data table
  3. Applications

Publication details

Authors
Shenglin
Publisher
Shenglin
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Shenglin Shenglin CRCC / CRCC-E chilled-water in-row cooling. Shenglin. https://shenglin-tech.com/Precision%20AC/In_row_Cooling/InRow-Chilled-Water-Cooling.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace