SHSL-D1 dry cooler technical parameters
Shenglin
The Shenglin SHSL-D1 horizontal-discharge dry cooler series spans 5-649 kW and 2828-263503 m³/h of air, with separate capacity tables for water and 20% glycol.
On this page
Overview
Shanghai Shenglin M&E Technology presents the SHSL-D1 as a horizontal air discharge dry cooler. The performance range on the page is 5 to 649 kW cooling capacity, 2828 to 263503 m³/h air volume and 31 to 69 dB(A) sound pressure level at 10 m. Custom dry coolers are available on request.
Design features: high-efficiency heat exchanger, maximum 100 kPa coil pressure drop on the medium side at water design condition, low-specific-energy fans, IP54 motors with class F insulation, 400V/3N/50Hz supply and an air separator for each fan. Heat exchangers ship clean and are tested at 30 bar. Options include water, oil or glycol coils, multiple circuits, sub-cooling circuits, stainless or aluminium casing, coated aluminium or copper fins, explosion-proof motors and customised fin spacing.
The technical parameter tables cover models with 2.1 mm fin spacing; model names run from SHSL-D1-005-1x350 to SHSL-D1-334-8x630, where the suffix gives fan count and fan diameter in mm. For each model the tables give capacity at 35°C outdoor air with 45°C inlet and 40°C outlet for water and for 20% glycol, in separate columns for delta and star fan connections, plus water flow, pressure drop and air flow.
For example, SHSL-D1-005-1x350 gives 4.89 kW on water and 4.72 kW on 20% glycol, with 0.85 m³/h water flow, 36 kPa pressure drop and 2828 m³/h air flow. SHSL-D1-020-1x500 gives 19.80 kW on water and 19.29 kW on 20% glycol at 3.5 m³/h.
Key points
- Series: SHSL-D1 horizontal air discharge dry cooler; capacity 5-649 kW.
- Air volume 2828-263503 m³/h; sound pressure 31-69 dB(A) at 10 m.
- Medium-side pressure drop is at most 100 kPa at water design condition.
- Heat exchangers are tested at 30 bar before delivery.
- Fan motors are IP54, class F, 400V/3N/50Hz.
- Table condition: 35°C outdoor air, medium 45°C in and 40°C out, fin spacing 2.1 mm.
- SHSL-D1-005-1x350 gives 4.89 kW on water and 4.72 kW on 20% glycol.
- SHSL-D1-020-1x500 gives 19.80 kW on water and 19.29 kW on 20% glycol at 3.5 m³/h.
- Separate capacity columns exist for delta and star fan connections.
Using it in design
- Read capacity for the actual fluid: 20% glycol gives less kW than water in the same model (4.72 kW against 4.89 kW).
- Compare design ambient temperature with the 35°C table point; request capacity corrections from the manufacturer for other temperatures.
- Because delta or star fan connection changes capacity, state the connection type in the order specification.
- The page title states horizontal discharge while the standard air discharge footnote shows a different direction, so confirm the order direction with the manufacturer.
- Add the medium-side pressure drop (for example 36 kPa) to pump selection.
Who should read it
Mechanical designers selecting dry coolers for chilled-water heat rejection and evaluating glycol-fluid capacity.
Document contents
- Features
- Technical Data
- Application
- Certification
- Part List
- Reference
- Technical parameter: SHSL-D1 series (fin space 2.1 mm)
Publication details
- Authors
- Shenglin
- Publisher
- Shenglin
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document