Technical guideFree to read2026

Shenling Air-cooled Screw Chiller (Heat Pump), 7 March 2026 catalogue

Original title Shenling Air-cooled Screw Chiller (Heat Pump) 20260307, printed p.11 (PDF p.8)

Shenling

Shenling's March 2026 catalogue gives inverter-driven twin-screw air-cooled chillers in R134a (357-1,339 kW) and R407C (about 333-1,568 kW) series, rated at 7 °C leaving water and 35 °C ambient.

On this page

Overview

The catalogue presents Guangdong Shenling Environmental Systems' (stock code 301018) inverter-driven screw air-cooled chiller and heat pump products. The company, founded in 2000, states over 1,000 engineers, 420,888 m² of production area, over 300 Fortune 500 clients and over 10,000 global projects. The model code (for example LSRF360AST-VFAE) encodes product type, heat pump function, air cooling, capacity (kW), refrigerant (H: R407C, A: R134a), function, start method (V: variable frequency) and power supply (380 V/3N~/50 Hz).

Technical features include a high-efficiency twin-screw compressor with 5:6 asymmetric rotors, micron-level machining, motor cooling by refrigerant, a built-in three-stage oil separator (over 99.9% separation efficiency, with 99.99% also quoted in the text), slide valve capacity control from 25% to 100% stepless and 0, 50, 75, 100% staged, an electronic expansion valve and variable frequency starting. Variable frequency starting markedly reduces starting current compared with star-delta, direct-on-line and soft starting.

The product parameter table lists 16 models in the R134a high-efficiency series with nominal cooling capacity 357 to 1,339 kW and cooling COP of about 3.28-3.39. The R407C series has 17 models, capacity 332.6 to 1,568.2 kW and COP 2.93-3.02. The rating condition is user-side leaving water 7 °C, water flow 0.172 m³/(h kW) and heat-source ambient 35 °C; for heating, leaving water 45 °C and source 7/6 °C dry/wet bulb. Evaporator pressure drop excludes external pipes and components.

The catalogue also covers installation clearances, operating range (heating at -10 to 0 °C ambient with R134a should be referred to the factory), system water volume calculation, capacity correction factors (low water temperature, glycol, altitude), a maintenance table and project cases. The weight table separates cooling and heat pump versions; the inverter wording in the heading and the star-delta start row should be confirmed with the manufacturer.

Key points

  1. R134a high-efficiency series: 16 models, 357 to 1,339 kW nominal cooling.
  2. R407C series: 17 models, 332.6 to 1,568.2 kW nominal cooling.
  3. Rating condition: 7 °C leaving water, 0.172 m³/(h kW) flow, 35 °C ambient.
  4. COP: about 3.28-3.39 in the R134a series; 2.93-3.02 in the R407C series.
  5. Capacity control by slide valve 25-100% stepless; staged 0, 50, 75, 100%.
  6. Oil separation efficiency over 99.9%; three-stage separator.
  7. Variable frequency starting markedly reduces starting current versus star-delta and direct-on-line.
  8. Power supply 380 V/3N~/50 Hz.
  9. Capacity correction factors: low water temperature, glycol, altitude.

Using it in design

  • Correct capacities from the 7 °C leaving water and 35 °C ambient rating to your design conditions; ask for the manufacturer's derating curve at high ambient.
  • If a data centre uses a higher chilled water temperature, check the leaving water operating range and capacity correction factors.
  • Calculate minimum system water volume with the catalogue formula; small volume risks unstable operation.
  • Add external pipe and valve losses to the evaporator pressure drop when sizing pump head.
  • Have the inverter and start method (variable frequency or star-delta) stated explicitly in the specification.

Who should read it

Mechanical designers and procurement engineers selecting air-cooled screw chillers.

Document contents

  1. Company profile
  2. Product overview
  3. Energy-efficient, stable and reliable
  4. Professional design, eco-friendly
  5. Product parameters
  6. Installation space requirements and operating range
  7. System water capacity, capacity correction factor and maintenance
  8. Performance cases

Publication details

Authors
Shenling
Publisher
Shenling
Year
2026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Shenling (2026). Shenling Air-cooled Screw Chiller (Heat Pump) 20260307, printed p.11 (PDF p.8). Shenling. https://img.shenlinghvac.com/attachment/1/file/6225/Shenling%20Air-cooled%20Screw%20Chiller(Heat%20Pump)_Ver.20260307.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.