Soeteck Fan Wall Precision Air Conditioning: FO.GBE, FO.WL and FOAC, 2024
Original title SOETECK Fan Wall Precision Air Conditioner
SOETECK
Soeteck's 2024 brochure presents chilled-water fan wall units (FO.GBE, FO.WL) from 30 to 300 kW and FOAC units of 100 and 200 kW, claiming over 10% fan power savings with hot aisle containment and MTBF above 100,000 hours.
On this page
Overview
The document is a 2024 brochure for Soeteck's fan wall precision air-conditioning products for data centers. A fan wall unit embeds the cooling coil and an EC fan matrix in the data hall's isolation wall to form a closed hot aisle, so hot air from the servers enters the unit directly. The brochure covers the modular FO.GBE fan wall, the FO.WL fan wall air conditioning wall and the FOAC chilled water solution.
The FO.GBE series are modules of 150, 200, 250 and 300 kW (at 37 °C, 30% RH) on 15/21 °C water, with 35,000 to 56,000 m³/h airflow, 200 Pa residual pressure and sizes of 2400 or 3000 x 1100 x 2150 mm. The FO.WL units are smaller, at 60 and 30 kW (18/24 °C water). FOAC is a modular, stackable 100 and 200 kW unit that delivers air directly to the cold aisle without a raised floor.
The manufacturer states that a fan wall saves over 10% energy through lower fan pressure loss at the same airflow, can raise capacity by up to 100% in the same size, and saves 50% of floor area at the same capacity. For white space it describes direct fresh air, fresh air and return air mixing, and indirect evaporative cooling options. The figures are manufacturer claims with no independent measurement.
Key points
- FO.GBE modular fan wall: 150.10, 200.10, 250.10 and 300.10 kW (37 °C, 30% RH), 15/21 °C water, water flow 21.51 to 43.01 m³/h, pressure drop 115 to 130 kPa.
- FO.GBE airflow is 35,000, 40,000, 49,000 and 56,000 m³/h at 200 Pa residual pressure, with 4 or 6 EC fans and rated power of 7.00 to 13.20 kW.
- FO.WL: 60.10 kW (78 fans, 14,100 m³/h, 1.04 kW) and 30.20 kW (39 fans, 7,000 m³/h, 0.39 kW); 18/24 °C water; weight 165 and 95 kg.
- FOAC: 100 CEH at 108.64 kW and 200 CEH at 217.27 kW gross capacity; sensible heat ratio 1; airflow 5.5 and 11 m³/s; sound 73 and 76 dBA; washable G4 MERV8 filter.
- FOAC rating: return air 35 °C and 25.4% RH, water 12/22 °C; no raised floor needed, with air delivered directly to the cold aisle.
- Manufacturer claim: fan wall cuts fan power by over 10% versus room-type air conditioning; capacity up to 100% higher in the same size; 50% floor area saved at the same capacity.
- Manufacturer claim: MTBF above 100,000 hours and design life above 15 years.
- Group control modes: rotation standby, same-direction autonomy, average distribution and on-demand distribution; MODBUS-RTU, MODBUS-TCP, SNMP and HTTP supported.
Using it in design
- In large halls, compare a hot-aisle-contained fan wall layout with room-type air conditioning on layout and floor area, and verify the manufacturer's claims with CFD and site data.
- Choose water temperature (15/21 °C, 18/24 °C, 12/22 °C) to match the facility water loop; a higher supply temperature increases free cooling hours.
- Capacity values are rated at 37 °C or 35 °C return air; recalculate capacity at your design return air.
- Include fan redundancy, group control modes and BMS protocols (MODBUS, SNMP) in the redundancy and monitoring design.
- For raised-floor-free solutions such as FOAC, assess ceiling height and cold aisle air distribution.
Who should read it
Mechanical designers and operators selecting fan wall or contained-aisle precision cooling for large data centers.
Document contents
- FO.WL fan wall air conditioning wall introduction
- Product features and structural design
- Group control and monitoring
- Application scenarios (new data center, retrofit, cold climate)
- Energy-saving features
- Technical parameters: FO.GBE and FO.WL
- FOAC series typical installation and technical specification
Publication details
- Authors
- SOETECK
- Publisher
- SOETECK
- Year
- 2024
- Document number
- FO240530(1.0V)
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
SOETECK (2024). SOETECK Fan Wall Precision Air Conditioner. SOETECK. FO240530(1.0V). https://soeteck.com/resources/Soeteck-Fan-Wall-Precision-Air-Conditioner.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.