SOETECK Chilled-Water In-Row Cooling System model table

Original title SOETECK Chilled-Water In-Row Cooling System

SOETECK

SOETECK's chilled-water in-row unit lists nine model rows across three sizes (025RC, 045RC, 065RC) and three water regimes (7/12, 10/15, 13/18 °C), from 32.9 to 93.2 kW.

On this page

Overview

The page presents SOETECK's chilled-water in-row cooling system for modular and containerised data centres. Capacity is modulated dynamically with motorised ball valves, which limits water cycling at low load. EC fans adjust airflow to the needs of the IT equipment. Width options are 300 mm and 600 mm.

Additional features include a precision cooling controller, touch-screen display, optional SNMP communication and dual power input. The page positions the 025RC for small to medium IT loads and the 065RC for high-density server setups.

The model table gives three bodies across three water regimes. 025RC (300 mm, 4,800 m³/h, 190 kg): 41.0 kW (7/12 °C), 36.8 kW (10/15 °C), 32.9 kW (13/18 °C). 045RC (600 mm, 9,000 m³/h, 330 kg): 65.4, 59.0, 52.4 kW. 065RC (600 mm, 11,400 m³/h, 400 kg): 93.2, 84.0, 74.8 kW. Sensible capacity equals or nearly equals total capacity in all models; depth is 1,100 mm and height 2,000 mm.

The capacity range in the page title (28.9-65.8 kW) differs from the table values; the summary strip gives total capacity 41.0-74.8 kW and sensible 40.8-74.8 kW (return air 40 °C / 18 % RH). The detailed technical specification section is not yet published on the page; the manufacturer brochure should be the basis for selection.

Key points

  1. Nine model rows: 025RC, 045RC and 065RC, each at 7/12, 10/15 and 13/18 °C water.
  2. 025RC: 41.0 / 36.8 / 32.9 kW; 045RC: 65.4 / 59.0 / 52.4 kW; 065RC: 93.2 / 84.0 / 74.8 kW.
  3. Air flow 4,800 (025RC), 9,000 (045RC), 11,400 m³/h (065RC).
  4. Width 300 mm (025RC) and 600 mm (045RC, 065RC); depth 1,100 mm; height 2,000 mm.
  5. Weight 190 / 330 / 400 kg.
  6. Motorised ball valve modulation, EC fans, touch screen, optional SNMP and dual power input.
  7. Moving water to 13/18 °C cuts capacity by about 20 % against 7/12 °C (025RC from 41.0 to 32.9 kW).

Using it in design

  • If you choose 10/15 or 13/18 °C instead of 7/12 °C water, capacity drops (025RC from 41.0 to 32.9 kW); carry this reduction into the unit count for high-temperature plant designs.
  • Because sensible capacity equals total capacity, select by sensible heat load.
  • Place the 300 mm and 600 mm widths in the row plan according to rack row and water connection points.
  • The capacity range differs between page title and table; obtain written confirmation of exact capacity from the manufacturer.
  • Order the dual power input and SNMP options for critical rows.

Who should read it

Mechanical engineers designing chilled-water in-row cooling.

Document contents

  1. Overview
  2. Key features
  3. Model range
  4. Models table
  5. Technical specifications (to be published)

Publication details

Authors
SOETECK
Publisher
SOETECK
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

SOETECK SOETECK Chilled-Water In-Row Cooling System. SOETECK. https://soeteck.com/en/products/thermal-management/precision-air-conditioning/soeteck-chilled-water-in-row-cooling-system-28-9kw-65-8kw-capacity/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.