SOETECK DX Air-Cooled In-Row Cooling System model table
Original title SOETECK DX Air-cooled In-Row Cooling System
SOETECK
SOETECK's DX in-row unit offers 11 models with inverter compressors and R410A, from 7.5 to 90.5 kW (SHR 100 %), 2,300-16,200 m³/h airflow and 300, 600 or 900 mm widths.
On this page
Overview
The page presents SOETECK's air-cooled DX in-row cooling system for modular and micro data centres and integrated IT systems. It is fitted with an inverter compressor, which keeps operation stable under variable heat loads, and EC fans that adjust airflow to the IT equipment. The refrigerant is R410A and the precision controller allows BMS integration.
Options include a condensate pump and a long piping kit. Modulation prevents the compressor from cycling frequently at low load. Width options are 300, 600 and 900 mm.
The model table has 11 models: 007RA 7.5 kW, 012RA 12.6 kW, 017RA 17.8 kW, 020RA 21.5 kW, 025RA 25.5 kW, 030RA 31.5 kW, 040RA 41.5 kW, 050RA 50.5 kW, 065RA 65.5 kW, 075RA 75.5 kW and 090RA 90.5 kW. Sensible capacity equals total capacity. Air flow is 2,300 to 16,200 m³/h and weight 213 to 620 kg; depth is 1,100 mm and height 2,000 mm.
Width is 300 mm for 007-030RA, 600 mm for 040-065RA and 900 mm for 075 and 090RA. Although the page title states a 5.6-90.1 kW range, the table gives 7.5-90.5 kW. The detailed technical specification section is not yet published, and the ambient condition behind the capacity is not stated on the page.
Key points
- 11 models: 7.5 / 12.6 / 17.8 / 21.5 / 25.5 / 31.5 / 41.5 / 50.5 / 65.5 / 75.5 / 90.5 kW (007RA ... 090RA).
- SHR 100 %; sensible capacity equals total capacity.
- Air flow 2,300 to 16,200 m³/h.
- Width 300 mm (007-030RA), 600 mm (040-065RA), 900 mm (075-090RA); depth 1,100; height 2,000 mm.
- Weight 213 kg (007RA) to 620 kg (090RA).
- Inverter compressor, EC fan, R410A, precision controller and BMS integration.
- Options: condensate pump, long piping kit.
Using it in design
- With sensible capacity equal to total, select directly against the server heat load.
- The ambient condition for capacity is not given on the page, so confirm capacity for the indoor and outdoor temperatures with the manufacturer before ordering.
- Obtain the limits of the outdoor unit placement and the long piping kit (line length, height difference) from the manufacturer.
- Carry condensate drainage and the optional pump into the row layout.
- Match the width choice (300, 600, 900 mm) to the rack row length and weight.
Who should read it
Mechanical engineers designing DX in-row cooling.
Document contents
- Overview
- Key features
- Model range
- Models table
- Technical specifications (to be published)
Publication details
- Authors
- SOETECK
- Publisher
- SOETECK
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
SOETECK SOETECK DX Air-cooled In-Row Cooling System. SOETECK. https://soeteck.com/en/products/thermal-management/precision-air-conditioning/soeteck-dx-air-cooled-in-row-cooling-system-5-6kw-90-1kw-capacity/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.