Technical guideFree to read2021

What Makes Submer's SmartCoolant So Smart? (Dielectric Fluid E-book)

Original title What makes Submer's SmartCoolant so smart? (eBook)

Submer · Peter Cooper

A 2021 vendor e-book in which Submer compares its single-phase immersion coolant SmartCoolant with mineral oil, vegetable oil and fluorocarbons on compatibility, safety, stability, biodegradability and thermal performance.

On this page

Overview

The e-book introduces the fluid options facing a new immersion cooling user (vegetable oils, mineral oils, fluorocarbons, synthetic hydrocarbons) and explains why Submer developed its own synthetic dielectric fluid. Five themes are covered: hardware compatibility, safety and easy handling, stability, biodegradability and high performance.

The vendor states that SmartCoolant has eight times the dielectric strength of air, is compatible with common metals and many plastics and elastomers, carries an NFPA flammability rating of 1 out of 4, does not evaporate because it is single-phase, and holds NSF HT1 food-grade certification. Its fully synthetic origin is presented as the stability argument, avoiding impurities that speed oxidation in mineral and vegetable oils; it adds that the fluid is readily biodegradable per OECD 301 with a GWP of 0.

The thermal table lists viscosity of 5 cSt at 40°C (fluorocarbon 2, mineral oil 12, vegetable oil >14), heat capacity of 1.1 kJ/kg K and thermal conductivity of 0.14 W/mK; the vendor links this to a three-degree drop in tank temperature against its previous coolant. Fluid life is rated up to 15 years and top-up cost is about EUR 5 per litre. The document is sales material without independent measurement, and its comparisons are the vendor's own assessment.

Key points

  1. Dielectric strength is 8 times that of air; NFPA flammability rating is 1 out of 4.
  2. Being single-phase, the fluid does not evaporate, so no costly ventilation or hermetic tank design is needed.
  3. NSF HT1 food-grade certification and ready biodegradability per OECD 301 are claimed, with a GWP of 0.
  4. At 40°C: viscosity 5 cSt, heat capacity 1.1 kJ/kg K, conductivity 0.14 W/mK (fluorocarbon: 2 cSt, 0.07 W/mK; mineral oil: 12 cSt, 0.13 W/mK).
  5. Fluid life is rated up to 15 years; fluid is topped up only when servers are added or removed, at about EUR 5 per litre.
  6. Tank temperature fell by three degrees against the previous coolant.
  7. The paper argues that mineral oils and fluorocarbons are not biodegradable and that fluorocarbons persist in the environment.

Using it in design

  • Compare viscosity, heat capacity and thermal conductivity together when choosing an immersion fluid; do not select on a single property such as low viscosity.
  • Request the vendor's compatibility data for cable sheathing, seals and elastomers, and check hardware warranty terms against fluid approval.
  • Design level sensors and a reservoir to manage fluid volume when servers are added or removed.
  • In fire-load and environmental review, verify flammability rating, biodegradability and GWP claims against independent documents.

Who should read it

Designers and decision makers selecting immersion cooling fluids and tank architectures.

Document contents

  1. Introduction
  2. Compatibility
  3. Safety and easy handling
  4. Stability
  5. Biodegradability
  6. High performance
  7. Q&A

Related standards

  • NFPA 704

Publication details

Authors
Peter Cooper
Publisher
Submer
Year
2021
Document number
EB07
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Vendor eBook on submer.com; no open licence stated

Citation

Peter Cooper (2021). What makes Submer's SmartCoolant so smart? (eBook). Submer. EB07. https://submer.com/wp-content/uploads/2021/04/EB07_What_Makes_Submers_SmartCoolant_So_Smart.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.