The Convection Principle: What It Is and How It Applies to Submer's Immersion Cooling Technology
Original title The Convection Principle: What it is and how it applies to Submer's Immersion Cooling Technology (White paper)
Submer
A 2020 Submer white paper by its senior thermal engineer that uses Newton's law of cooling to explain convection and why a single-phase dielectric liquid gives a far higher heat transfer coefficient than air in immersion cooling.
On this page
Overview
The white paper opens by noting that conventional electronics cooling relies on accelerated air, channels and heatsinks, but that excess cooling effort wastes energy, raises cost and adds maintenance. Because air is a good insulator and water is incompatible with electronics, it argues for replacing air with a dielectric liquid, namely Submer's proprietary synthetic SmartCoolant.
The technical section separates conduction, convection and radiation and defines convection as energy transport by moving particles. Heat transfer is modelled with Newton's law of cooling (heat transfer coefficient, surface area and the temperature difference between solid and fluid). Specific heat sets how much energy a fluid can carry, and liquids beat gases because they are denser.
Three ways to raise convection are listed: use a colder fluid, enlarge the surface with fins and pins, or choose a fluid with a higher heat transfer coefficient. Typical coefficient ranges are given; according to the author, flat-plate studies of SmartCoolant give a natural-convection coefficient of about 500 W/m2K. The document is a principles explanation written by the vendor; it contains no measured per-server cooling capacity or comparative test results.
Key points
- Typical heat transfer coefficient ranges: free convection in air 0.5-1000 W/m2K, in liquids 50-3000 W/m2K.
- Forced convection: air 10-1000 W/m2K, water and liquids 50-10000 W/m2K, liquid metals 5000-40000 W/m2K.
- Boiling water spans 3000-100000 W/m2K and condensing water vapour 5000-100000 W/m2K.
- For SmartCoolant the base natural-convection coefficient is given as about 500 W/m2K, against about 0.5 for air.
- Three ways to raise convection: colder fluid, larger surface (fins, pins) and a fluid with a higher coefficient.
- Accelerating the liquid raises its heat extraction, so immersion can start without fans and add flow if more cooling is needed.
- Convection is modelled with Newton's law of cooling: heat flow equals coefficient times surface times temperature difference.
Using it in design
- When comparing immersion with air cooling, use the heat transfer coefficient ranges (one to three orders of magnitude between air and liquid) as a first assumption.
- Re-optimise heatsink geometry for the liquid, remembering that added surface also brings a conduction effect.
- Treat tank fluid inlet temperature, the easiest lever on the temperature difference, as the primary control variable in heat rejection design.
- Verify vendor coefficient curves at your own flow velocity and geometry; do not carry flat-plate data directly to server level.
Who should read it
Designers and decision makers who want the physical basis of immersion cooling.
Document contents
- Introduction
- Operational driver (gas, liquid or solid)
- Submer's SmartCoolant
- The convection principle (how it works, maximizing convection)
- Conclusions
- About Submer
Publication details
- Authors
- Submer
- Publisher
- Submer
- Year
- 2020
- Document number
- WP01
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Vendor white paper on submer.com; no open licence stated
Citation
Submer (2020). The Convection Principle: What it is and how it applies to Submer's Immersion Cooling Technology (White paper). Submer. WP01. https://submer.com/wp-content/uploads/2020/10/WP01-TheConvectionPrinciple.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.