Submer 2025 COOLERCHIPS Annual Review Presentation: Immersion Cooling Overview

Original title Submer presentation - 2025 ARPA-E COOLERCHIPS Annual Review

Submer (hosted by ARPA-E) · Ryan Howard

Submer's November 2025 COOLERCHIPS talk compares air, DLC and single/two-phase immersion, citing 100% heat capture for immersion, about 60% for DLC and up to 361 kW for SmartPod EXO.

On this page

Overview

The deck is a Submer slide set presented at the ARPA-E COOLERCHIPS 2025 annual review (20-21 November 2025, St. Louis). It starts from next-generation HPC and AI hardware requirements: CPU and GPU TDPs keep rising and other components heat up as well. Air cooling limits are described; immersion offers 100% heat capture with liquid in direct contact, while direct liquid cooling (DLC) captures roughly 60%.

Four main technologies (air-to-air, DLC, single-phase immersion, two-phase immersion) are compared with pros and cons. For DLC it lists complexity, leak risk, large copper quantities and vendor lock-in; for two-phase it highlights health risk, PFAS, over-engineered tanks and expensive fluid (about $90/kg). Single-phase immersion is positioned as simple, reliable, future-proof and competitive on TCO.

For the Submer SmartPod EXO it states 99.999% (5x9) availability and concurrent maintainability (needing a Twin Tank with external ATS and UPS), up to 361 kW heat dissipation with a Unitank, heat reuse and free-cooling optimisation, and the chance to eliminate direct water use. A 1.2 MW section example uses 4 SmartPod EXO Twintanks and 3 dry coolers of 600 kW. The document is a vendor presentation; comparisons reflect Submer's viewpoint.

Key points

  1. Immersion gives 100% heat capture; direct liquid cooling (DLC) roughly 60%.
  2. SmartPod EXO: 99.999% (5x9) availability and concurrent maintainability, needing a Twin Tank with external ATS and UPS.
  3. A SmartPod EXO Unitank can dissipate up to 361 kW (under specific operating conditions).
  4. Example 1.2 MW section: 4 SmartPod EXO Twintanks and 3 dry coolers of 600 kW with a redundant warm water loop.
  5. Two-phase fluid is cited at about $90/kg with PFAS regulatory risk.
  6. CPUs trend toward 200-400 W and GPUs toward 1200-1400 W.
  7. The joint work with Intel points to immersion for TDP above 1000 W.
  8. Water savings up to 99% are cited; PDUs sit in the rear dry zone.

Using it in design

  • When choosing between DLC and immersion, weigh heat capture (about 60% vs 100%) against the load left to air cooling.
  • Specify the wet and dry zone split (PDUs in the dry zone) and capillarity-prevention panels in immersion designs.
  • In dry-cooler designs, plan warm water loop redundancy at section scale (for example 1.2 MW).
  • Check which hardware configuration (Twin Tank, ATS, UPS) backs the 5x9 availability claim.
  • Verify vendor comparisons against independent data.

Who should read it

Engineers selecting cooling technology for high-density HPC and AI sites and investment decision makers.

Document contents

  1. Requirements for next-generation HPC/AI hardware
  2. Overview of main cooling technologies
  3. Immersion overview
  4. SmartPod EXO: how does it work
  5. Immersion advantages
  6. Heat reuse opportunities and dry cooling example
  7. How Submer solutions address industry challenges

Publication details

Authors
Ryan Howard
Publisher
Submer (hosted by ARPA-E)
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Company presentation hosted on arpa-e.energy.gov; authored by a private company, not a US federal work

Citation

Ryan Howard (2025). Submer presentation - 2025 ARPA-E COOLERCHIPS Annual Review. Submer (hosted by ARPA-E). https://arpa-e.energy.gov/sites/default/files/2026-01/Day1_06d_Submer_Howard.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.