Submer 2025 COOLERCHIPS Annual Review Presentation: Immersion Cooling Overview
Original title Submer presentation - 2025 ARPA-E COOLERCHIPS Annual Review
Submer (hosted by ARPA-E) · Ryan Howard
Submer's November 2025 COOLERCHIPS talk compares air, DLC and single/two-phase immersion, citing 100% heat capture for immersion, about 60% for DLC and up to 361 kW for SmartPod EXO.
On this page
Overview
The deck is a Submer slide set presented at the ARPA-E COOLERCHIPS 2025 annual review (20-21 November 2025, St. Louis). It starts from next-generation HPC and AI hardware requirements: CPU and GPU TDPs keep rising and other components heat up as well. Air cooling limits are described; immersion offers 100% heat capture with liquid in direct contact, while direct liquid cooling (DLC) captures roughly 60%.
Four main technologies (air-to-air, DLC, single-phase immersion, two-phase immersion) are compared with pros and cons. For DLC it lists complexity, leak risk, large copper quantities and vendor lock-in; for two-phase it highlights health risk, PFAS, over-engineered tanks and expensive fluid (about $90/kg). Single-phase immersion is positioned as simple, reliable, future-proof and competitive on TCO.
For the Submer SmartPod EXO it states 99.999% (5x9) availability and concurrent maintainability (needing a Twin Tank with external ATS and UPS), up to 361 kW heat dissipation with a Unitank, heat reuse and free-cooling optimisation, and the chance to eliminate direct water use. A 1.2 MW section example uses 4 SmartPod EXO Twintanks and 3 dry coolers of 600 kW. The document is a vendor presentation; comparisons reflect Submer's viewpoint.
Key points
- Immersion gives 100% heat capture; direct liquid cooling (DLC) roughly 60%.
- SmartPod EXO: 99.999% (5x9) availability and concurrent maintainability, needing a Twin Tank with external ATS and UPS.
- A SmartPod EXO Unitank can dissipate up to 361 kW (under specific operating conditions).
- Example 1.2 MW section: 4 SmartPod EXO Twintanks and 3 dry coolers of 600 kW with a redundant warm water loop.
- Two-phase fluid is cited at about $90/kg with PFAS regulatory risk.
- CPUs trend toward 200-400 W and GPUs toward 1200-1400 W.
- The joint work with Intel points to immersion for TDP above 1000 W.
- Water savings up to 99% are cited; PDUs sit in the rear dry zone.
Using it in design
- When choosing between DLC and immersion, weigh heat capture (about 60% vs 100%) against the load left to air cooling.
- Specify the wet and dry zone split (PDUs in the dry zone) and capillarity-prevention panels in immersion designs.
- In dry-cooler designs, plan warm water loop redundancy at section scale (for example 1.2 MW).
- Check which hardware configuration (Twin Tank, ATS, UPS) backs the 5x9 availability claim.
- Verify vendor comparisons against independent data.
Who should read it
Engineers selecting cooling technology for high-density HPC and AI sites and investment decision makers.
Document contents
- Requirements for next-generation HPC/AI hardware
- Overview of main cooling technologies
- Immersion overview
- SmartPod EXO: how does it work
- Immersion advantages
- Heat reuse opportunities and dry cooling example
- How Submer solutions address industry challenges
Publication details
- Authors
- Ryan Howard
- Publisher
- Submer (hosted by ARPA-E)
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Company presentation hosted on arpa-e.energy.gov; authored by a private company, not a US federal work
Citation
Ryan Howard (2025). Submer presentation - 2025 ARPA-E COOLERCHIPS Annual Review. Submer (hosted by ARPA-E). https://arpa-e.energy.gov/sites/default/files/2026-01/Day1_06d_Submer_Howard.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.