High-Performance Computing Data Center Cooling System Energy Efficiency (ESIF)
National Laboratory of the Rockies (formerly NREL) · National Laboratory of the Rockies
This page walks through the ESIF HPC data center cooling system in schematic steps: liquid cooling via CDUs for most heat, fan walls for residual air-cooled load, a closed energy-recovery water loop and a hierarchy of heat rejection.
On this page
Overview
The source is a web page from the National Laboratory of the Rockies (formerly NREL) describing the cooling system of the ESIF high-performance computing (HPC) data center; it was last updated on 17 February 2026. The page is a schematic walk-through that explains each step of the system in order. The first principle of the system is that most of the heat is captured by liquid.
Operators require 90% or more of IT heat to be captured by liquid cooling, and fan walls handle the residual air-cooled load. Cooling distribution units (CDUs) supply coolant at the temperature, pressure and chemistry the IT needs. This shows that the liquid capture fraction can be a design target in liquid-cooled halls. A hierarchy is defined for heat rejection. Heat is first reused as building process hot water, then sent to a thermosyphon dry cooler and finally to cooling towers.
The system also includes a closed energy-recovery water loop. The ordering follows the logic of using the most efficient available option first, to reduce energy and water consumption. The source is a presentation of a single facility, which means it is the practice of one research facility rather than a general standard or calculation method. The 90% capture rate should therefore be read as this facility's operating requirement and not as a universal rule. The page gives no detailed capacity, flow or temperature values, so this record contains none either.
Key points
- Operators require 90% or more of IT heat to be captured by liquid cooling.
- Cooling distribution units supply coolant at the temperature, pressure and chemistry the IT needs.
- Fan walls handle the residual air-cooled load.
- A closed energy-recovery water loop is used.
- Heat rejection hierarchy: reuse as building process hot water, then thermosyphon dry cooler, then cooling towers.
- The page was last updated on 17 February 2026.
- The source describes one facility's practice; it is not a general standard.
Using it in design
- Model heat rejection as a priority chain (reuse, dry cooler, evaporative tower) with hourly switching.
- Allow a 'minimum liquid capture fraction' design parameter for liquid-cooled halls.
- Design the layout so the residual air-cooled load is met by fan walls or a similar solution.
- Keep temperature, pressure and chemistry requirements as selection criteria when selecting CDUs.
- Assess heat reuse by matching it to the building's process hot water demand.
Who should read it
Mechanical engineers designing cooling and heat rejection for liquid-cooled, high-density HPC data centers.
Publication details
- Authors
- National Laboratory of the Rockies
- Publisher
- National Laboratory of the Rockies (formerly NREL)
- Year
- 2026
- Document language
- English
- Source type
- Government / public
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
NREL/NLR (contractor-operated DOE laboratory) web page; not US-Gov public domain. Cited only.
Citation
National Laboratory of the Rockies (2026). High-Performance Computing Data Center Cooling System Energy Efficiency (ESIF). National Laboratory of the Rockies (formerly NREL). https://www.nlr.gov/computational-science/data-center-cooling-system
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.