Fan Noise Reduction using Acoustic Metamaterials towards Efficient Data Centers
Trinity College Dublin / author conference manuscript · Sahan Wasala, Wenguang Zhao et al.
A two-page Trinity College Dublin manuscript showing that stackable metamaterial rings added to an 80 mm fan cut a targeted 4150 Hz tone by about 10.8 dB with six rings in this setup.
On this page
Overview
The manuscript combines acoustic simulation with a fan experiment and studies add-on metamaterial rings aimed at reducing a selected tone relevant to storage-system noise. An 80 mm fan and stackable rings were tested.
In the experimental setup six rings reduced the targeted 4150 Hz tone by about 10.8 dB. The paper is a short author conference manuscript demonstrating a passive, add-on approach to reducing data center fan noise.
Key points
- The work combines acoustic simulation with a fan experiment.
- An 80 mm fan and stackable metamaterial rings were tested.
- The targeted tone is 4150 Hz, relevant to storage-system noise.
- Six rings reduced the targeted tone by about 10.8 dB in this setup.
Using it in design
- Where storage or server racks have a specific tonal noise problem, assess tone-targeted passive add-ons at fan level as an alternative to broadband silencers.
- Do not adopt rings added to a fan without measuring their effect on airflow resistance; test flow and pressure loss together.
- In rooms with a noise target, measure the tone frequency and choose the solution to match it.
Who should read it
Acoustic and mechanical engineers investigating ways to reduce data center fan noise.
Related standards
- ISO 10302-1:2011
Publication details
- Authors
- Sahan Wasala; Wenguang Zhao; Oluwaseyi Ogun; Lon Stevens; Raye Sosseh; John Kennedy; Tim Persoons
- Publisher
- Trinity College Dublin / author conference manuscript
- Year
- Year not stated
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official university PDF opened with web tool; local curl returned 403. No year is printed in the inspected PDF, so year is null. No redistribution licence verified. Only authors’ own experiment summarized; ASHRAE citation not used.
Citation
Sahan Wasala; Wenguang Zhao; Oluwaseyi Ogun; Lon Stevens; Raye Sosseh; John Kennedy; Tim Persoons Fan Noise Reduction using Acoustic Metamaterials towards Efficient Data Centers. Trinity College Dublin / author conference manuscript. https://www.tara.tcd.ie/tara8/server/api/core/bitstreams/fa780d9f-b8aa-4eb3-8e3e-ecfdb0e8744c/content
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.