Research paperFree to read2024

IoT Based Real Time Monitoring System for Data Center Indoor Conditions

Original title Veri Merkezi İç Ortam Koşulları için IoT Tabanlı Gerçek Zamanlı İzleme Sistemi

Osmaniye Korkut Ata Üniversitesi Fen Bilimleri Enstitüsü Dergisi · Hakan Üçgün, Büşra Parlak et al.

A 2024 OKU Journal of The Institute of Science and Technology paper presents a low-cost IoT system on a Raspberry Pi 3 that monitors temperature, humidity, sound, motion, flame and liquid sensors and emails alerts on abnormal conditions.

On this page

Overview

The paper describes how researchers at Bilecik Seyh Edebali University built a low-cost system to monitor indoor parameters of a data-centre room remotely and in real time. The reasoning is that rooms housing servers need constant supervision and that a single device problem can disrupt data-centre operations. It was published in 2024 in the OKU Journal of The Institute of Science and Technology.

The system is built on a Raspberry Pi 3 mini computer. The sensing unit has a DHT11 temperature and humidity sensor, a sound sensor, a PIR motion sensor, a flame sensor for fires in the 760-1100 nm wavelength range, and a liquid-level sensor. Values are stored with timestamps in a MySQL database on Raspbian and shown live in a web interface, with a time-range chart for temperature and humidity.

Each sensor was tested and calibrated individually, followed by laboratory work with the integrated system. The system is powered by a 5 V adapter and uses a wired internet connection. When any parameter goes outside its set threshold, an email is sent to the user registered as administrator. The flame, motion, sound and liquid sensors work on a present/absent basis.

The work is a prototype with laboratory validation; it gives no numeric accuracy, latency or field-scale results. DHT11-class sensors and a single board would be limited in redundancy and accuracy for production facilities. It still offers a concrete example of a low-cost environmental monitoring and email-alarm architecture for small server rooms.

Key points

  1. Platform: Raspberry Pi 3, Raspbian, MySQL database and a web interface.
  2. Six parameters are monitored: temperature, humidity, sound intensity, motion, flame and liquid leakage.
  3. Sensors: DHT11 (temperature and humidity), sound sensor, PIR motion sensor, 760-1100 nm flame sensor, liquid-level sensor.
  4. On an abnormal condition the administrator user receives an email alert.
  5. Each sensor was tested and calibrated separately before integrated laboratory testing.
  6. The system runs on a 5 V adapter and a wired internet connection.
  7. Flame, motion, sound and liquid sensors give present/absent outputs.
  8. The paper is a prototype and contains no numeric performance metric.

Using it in design

  • For small server rooms, define temperature, humidity, liquid, smoke or flame and door-motion monitoring as the minimum environmental monitoring package.
  • Write requirements for alarm thresholds and more than one alert channel, not email alone.
  • For production facilities, require calibration-certified sensors rather than DHT11-class low-cost devices.
  • Include redundancy and a UPS-backed power supply for the monitoring system itself in the design.
  • Write in the acceptance procedure that each sensor is tested individually and then passes an integrated test.

Who should read it

Small server-room operators, environmental monitoring system designers and students reviewing low-cost IoT monitoring.

Document contents

  1. Introduction
  2. Literature Review
  3. Materials and Methods: Raspberry Pi 3, sensing unit, database design, user interface design
  4. Findings
  5. Discussion and Conclusions

Publication details

Authors
Hakan Üçgün; Büşra Parlak; Cihan Karakuzu
Publisher
Osmaniye Korkut Ata Üniversitesi Fen Bilimleri Enstitüsü Dergisi
Year
2024
Document number
7(2), 662–673
Document language
Turkish
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Tam metin yayıncının veya üniversitenin açık kaynağından okundu. Açık erişim, ticari yeniden dağıtım izni olarak yorumlanmadı; yalnızca bağlantı, metadata ve özgün kısa özet tutulur.

Citation

Hakan Üçgün; Büşra Parlak; Cihan Karakuzu (2024). Veri Merkezi İç Ortam Koşulları için IoT Tabanlı Gerçek Zamanlı İzleme Sistemi. Osmaniye Korkut Ata Üniversitesi Fen Bilimleri Enstitüsü Dergisi. 7(2), 662–673. https://doi.org/10.47495/okufbed.1342928

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Redundancy scenarios in SoSo CAD

Compare normal operation with equipment failures and see served loads and capacity shortfalls in the same view.

Normal operation and failure scenario comparison in SoSo CAD

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.