Rethinking Water Usage in Data Centers
Trane · Trane Technologies
A Trane white paper (DC-WPR004A) comparing open towers, air-cooled chillers, dry fluid coolers and adiabatic assist on the water-energy balance; adiabatic assist uses 70-80% less water than open towers.
On this page
Overview
The white paper explains how water use shapes data-centre chiller plant design. Open cooling towers rely on wet bulb temperature, giving lower lift, lower power draw and higher efficiency, but they lose water through evaporation, drift and blow down. Rough estimates are about 0.0224 gpm/ton for evaporation, 0.0004 for drift and 0.0108 for blow down, about 0.0336 gpm/ton in total.
At scale the loss is large: a 50 MW data centre may consume more than 475 gallons per minute and a 1 GW facility more than 9,500 gallons per minute. Air-cooled chillers use no water but depend on dry bulb temperature, giving larger lift and lower efficiency, and they come in smaller unit capacities; they can be fitted with low-compression free cooling or waterside economizers.
A second route to zero water is to pair water-cooled chillers with dry fluid coolers instead of an open tower, at the cost of higher power use and a large footprint. A third is adiabatic assist on dry coolers or air-cooled chillers: wetted media operates only at high ambient temperatures, reduces the number of units and cuts total water by 70-80% versus open towers. The customer chooses the activation temperature by balancing WUE against partial PUE (pPUE).
The paper gives demonstrative WUE and pPUE trade-off values for Albuquerque (hot, dry) and Chicago (cool, humid) and notes actual results may vary. It concludes that plant options should be tailored to facility size, local ambient conditions and customer priorities. It is a manufacturer white paper and refers to Trane products.
Key points
- Open tower make-up is roughly 0.0336 gpm/ton: evaporation 0.0224, drift 0.0004, blow down 0.0108 gpm/ton.
- A 50 MW data centre may consume over 475 gallons/minute and a 1 GW facility over 9,500 gallons/minute.
- Open towers use wet bulb temperature: low lift, low power draw, high efficiency.
- Air-cooled chillers use no water; efficiency drops because of dry bulb dependence and unit capacity is smaller.
- A waterside economizer reduces or removes compressor power when return water is warmer than ambient.
- Water-cooled chillers with dry fluid coolers eliminate water; the cost is more power and a large footprint.
- Adiabatic assist cuts total water by 70-80% versus open towers and operates only at high ambient temperatures.
- The activation temperature is selected by balancing WUE and partial PUE (pPUE).
Using it in design
- When selecting the cooling plant, set WUE and pPUE together as targets and run a climate-specific comparison as in the Albuquerque and Chicago examples.
- On water-constrained sites, evaluate dry fluid coolers or air-cooled options with their power and footprint impact.
- If adiabatic assist is used, set the activation ambient threshold from the WUE target and account for fan pressure drop.
- If an open tower is chosen, size make-up water (evaporation, drift, blow down) with gpm per ton values and declare it as the demand to the utility.
- For air-cooled chillers, verify per product whether a waterside economizer option exists.
Who should read it
Mechanical engineers designing data-centre cooling plants and operators weighing the water-energy balance.
Document contents
- Open Loop Cooling Towers: High Water Consumption
- Closed Loop Air-Cooled Chillers: Zero Water Consumption
- Closed Loop Water-Cooled Chillers: Zero Water Consumption
- Adiabatic Assist: Minimal Water Consumption
- Conclusion
Publication details
- Authors
- Trane Technologies
- Publisher
- Trane
- Year
- 2026
- Document number
- DC-WPR004A-EN
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
© 2026 Trane. All Rights Reserved (p. 6)
Citation
Trane Technologies (2026). Rethinking Water Usage in Data Centers. Trane. DC-WPR004A-EN. https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/White%20Paper/DC-WPR004A-EN_04162026.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.