Technical guideFree to read2009

Engineering Methods for the Dimensioning of Systems for the Removal of Smoke from Buildings

Original title Binalarda Duman Çekme Sistemlerinin Boyutlandırılması

Türk Tesisat Mühendisleri Derneği · Nejat Demircioğlu (çeviri)

TTMD's March-April 2009 supplement translating VDI 6019 Part 1: a smoke removal sizing method built on fire curves (t-squared growth, intensity coefficients from 0.0029 to 0.188 kW/s2).

On this page

Overview

The document is a Turkish translation of VDI guideline 6019 Part 1 (translated by Nejat Demircioglu), published as a supplement to issue 60 of the TTMD journal. It explains the basis and formulas behind fire curves used when verifying compliance of complex buildings by engineering calculation. It excludes pressurisation systems that provide smoke-safe escape routes.

Protection goals are escape conditions, support for firefighters and limiting damage. Criteria are a smoke-free layer of 2.5 m or more for at least 30 minutes, an average smoke-free layer temperature below 70 degrees, and minimal visibility-reducing and toxic gases. Smoke control rests on mass balance: air equal to the smoke extracted must be supplied, preferably at floor level.

The core is the fire curve. Phases are a constant 100 kW and 0.40 m2 fire area for the first 300 seconds, t-squared growth, steady burning, suppression effect and fire brigade intervention. Growth rate is slow, medium, fast or very fast with intensity coefficients of 0.0029, 0.012, 0.047 and 0.188 kW/s2, with example values by occupancy. Sprinkler activation times are tabulated by alpha value.

The method assumes horizontal fire areas; it does not suit liquid fires, vertical flame spread on racks, flashover or oxygen-poor fires, which need zone models or CFD. This is a 2009 translation and not data-centre specific, but it gives the calculation logic for smoke control in large-volume halls.

Key points

  1. Protection criterion: smoke-free layer at 2.5 m or higher for at least 30 minutes, with mean smoke-free layer temperature below 70 degrees.
  2. Fire intensity coefficient alpha (VdS 2827): slow 0.0029, medium 0.012, fast 0.047, very fast 0.188 kW/s2.
  3. For natural and powered smoke control, heat output is taken as a constant 100 kW over the first 300 seconds with an initial fire area of 0.40 m2.
  4. Fire growth follows Q = qf x A and A = (v x t)2, with area growing with the square of time.
  5. Table 2 gives heat output per unit area by use: offices 300, hotel rooms 250, retail 500, timber pallet storage 1250 kW/m2.
  6. Extracted smoke mass must be replaced by clean air, preferably from floor level; air inlets that are too high or too small disturb the smoke layer.
  7. Sprinkler activation times are given in Tables 5 to 8 for alpha 0.0029, 0.012, 0.047 and 0.188 kW/s2.
  8. The method does not apply to liquid fires, vertical rack fires, flashover or oxygen-starved fires.

Using it in design

  • State the smoke control criteria (smoke-free height, temperature, duration) explicitly in the design basis for large data halls and support spaces.
  • Select the fire growth coefficient for the hall's occupancy (slow to very fast) and include the sprinkler and suppression effect in the scenario.
  • Size exhaust flow by mass balance and place air inlets so they do not disturb the smoke layer.
  • Plan zone-model or CFD verification for cases outside the method, such as oil-filled equipment, high racks and oxygen-poor atmospheres.
  • Check the current edition of the guideline and the local fire regulation before use.

Who should read it

Mechanical engineers designing smoke control and ventilation, fire safety consultants and teams doing engineering-level fire calculations.

Document contents

  1. Introduction
  2. Scope and purpose: protection goals and smoke control concepts
  3. Terms and definitions
  4. Fire curves: method description, fire development and phases
  5. Sprinkler activation times
  6. Examples and application
  7. References

Publication details

Authors
Nejat Demircioğlu (çeviri)
Publisher
Türk Tesisat Mühendisleri Derneği
Year
2009
Document number
TTMD60 supplement38, March–April2009
Document language
Turkish
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official20-page PDF read. Page1 states VDI-TGA written translation permission; this is not redistribution permission for our library. Historical scope summary only; no current normative thresholds or ASHRAE content extracted.

Citation

Nejat Demircioğlu (çeviri) (2009). Binalarda Duman Çekme Sistemlerinin Boyutlandırılması. Türk Tesisat Mühendisleri Derneği. TTMD60 supplement38, March–April2009. https://www.ttmd.org.tr/upload/files/56688Dergi-Eki-60-1-1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.