USystems ColdLogik CL21 Rear Door Heat Exchanger Data Sheet, 2024

Original title ColdLogik CL21 Rear Door Heat Exchanger Data Sheet

Legrand / USystems · USystems

USystems' ColdLogik CL21 Smart Passive is a fanless passive rear door heat exchanger: with 14/20 °C water and 40 °C air on it cools up to 29 kW at 6,000 m³/h, at zero operating cost, with performance set by the rack equipment's fans.

On this page

Overview

The document is a 4-page data sheet for the USystems ColdLogik CL21 Smart Passive rear door heat exchanger (RDHx). The product runs on a closed-loop water circuit and removes heat from active equipment at the source in the rack. 'Smart Passive' means the unit has no fan of its own: performance depends entirely on the airflow produced by the active equipment in the cabinet and the available static pressure. The sheet stresses zero operating cost and suitability for data centers pursuing a sustainable operating structure.

Performance examples are given for two air-on conditions. At 40 °C dry-bulb air on, 14 °C water in and 20 °C water out, maximum duty is 7, 13, 17, 22, 25 and 29 kW at airflows of 1,000, 2,000, 3,000, 4,000, 5,000 and 6,000 m³/h. At 35 °C air on, the same airflows give 5, 10, 13, 17, 19 and 22 kW. Air pressure drop across the coil is 3.2 to 55.7 Pa, fluid flow 1 to 4.2 m³/h and fluid pressure drop 2.3 to 30 kPa (40 °C case).

Technical data covers 600, 750 and 800 mm wide versions for 42U, 47U and 52U racks with the interface frame: height 2000, 2222 and 2444 mm, depth 198 mm, dry weight (RDHx only) 55 to 85.1 kg, 83 to 120.1 kg with frame, and wet weight with frame 87.8 to 125.4 kg. The connection is 25 mm (1 inch) and water volume 4.8 L. Hinge side is left as standard, right on request; colour is RAL 9003 or 9005. The data are for illustration.

Key points

  1. CL21 Smart Passive is a passive RDHx: no fan, zero operating cost; performance depends on the rack's active equipment airflow and available static pressure.
  2. Cooling capacity of up to 29 kW is stated at 14 °C inlet water.
  3. 40 °C air on, 14/20 °C water: maximum duty 7, 13, 17, 22, 25 and 29 kW (at 1,000 to 6,000 m³/h).
  4. 35 °C air on, 14/20 °C water: maximum duty 5, 10, 13, 17, 19 and 22 kW (same airflows).
  5. Air pressure drop is 3.2 to 55.7 Pa; fluid flow 1 to 4.2 m³/h; fluid pressure drop 2.3 to 30 kPa (40 °C case).
  6. Height 2000, 2222, 2444 mm (42U, 47U, 52U); width 597, 747, 797 mm; depth 198 mm.
  7. Dry weight RDHx only 55 to 85.1 kg; with frame 83 to 120.1 kg; water connection 25 mm (1 inch), water volume 4.8 L.
  8. Hinge side left as standard, right on request; colour RAL 9003 (white) or RAL 9005 (black).

Using it in design

  • Establish the rack's active equipment airflow (m³/h) and available static pressure and read capacity from the table; the passive unit delivers capacity in line with the rack fans' airflow.
  • Between 35 and 40 °C air-on, capacity changes by about 20%; select against your own server exhaust temperature.
  • Match the 14/20 °C water temperature to the facility water loop; warmer water raises free cooling hours but lowers capacity.
  • In row layout, check the 198 mm depth, 55 to 125 kg weight and hinge side (left standard) against door swing and floor load.
  • Carry fluid pressure drop (2.3 to 30 kPa) and the 25 mm connection into manifold and pump selection.

Who should read it

Data center designers applying passive rear door cooling to medium-density racks and aiming to cut operating energy.

Document contents

  1. ColdLogik CL21 RDHx introduction
  2. Performance examples (40 °C and 35 °C air on)
  3. Technical data (42U, 47U, 52U)

Publication details

Authors
USystems
Publisher
Legrand / USystems
Year
2024
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

USystems (2024). ColdLogik CL21 Rear Door Heat Exchanger Data Sheet. Legrand / USystems. https://cdn.prod.website-files.com/65d3dd61583b600eeb976a07/66337982f1234ae4f45410b7_CL21%20Datasheet.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.