USystems ColdLogik CL23 HPC Rear Door Heat Exchanger Data Sheet, 2024
Original title ColdLogik CL23 Rear Door Heat Exchanger Data Sheet
Legrand / USystems · USystems
USystems' ColdLogik CL23 HPC is an active rear door heat exchanger giving up to 204 kW sensible cooling in a standard rack: 204 kW at 14/20 °C water, 177 kW at 20/30 °C and 164 kW at 23/33 °C, at 14,229 m³/h airflow.
On this page
Overview
The document is a 4-page data sheet for USystems' ColdLogik CL23 HPC rear door heat exchanger, designed for high-performance compute (HPC) loads. The product fits a standard IT rack, needs no specialist servers or infrastructure, can be retrofitted and has a small footprint. The maker positions it alongside direct-to-chip and immersion cooling and says it gives over 200 kW of sensible cooling per rack and can control the whole room environment without extra cooling equipment. EER at maximum duty is claimed to exceed 100.
The performance examples are three operating points of the same unit at different water temperatures, with air-on dry-bulb fixed at 65 °C and airflow of 14,229 m³/h (50 Hz, 230 V). Maximum duty at 14/20 °C water is 204 kW with 15 °C air off, 29.38 m³/h water flow and 4.84 m/s fluid velocity. Nominal duty at 20/30 °C water is 177 kW with 22.5 °C air off, 15.27 m³/h and 2.51 m/s. Efficient duty at 23/33 °C water is 164 kW with 26 °C air off, 14.2 m³/h and 2.34 m/s. The sheet says a 26 °C room temperature allows higher water temperatures and free cooling, with negligible capacity loss compared with nominal.
Technical data is given for 48U (fits 47U/48U rack) and 52U racks: height 2303 and 2481 mm, width 799 mm, depth 415 mm, dry weight 150 and 163 kg and wet weight 172 and 185 kg. Communication is Modbus over TCP/IP (BACnet and SNMP optional), connection 32 mm (1 1/4 inch), water volume 22 L and maximum current 16 A. Ten backward-curved centrifugal fans deliver 4,375, 10,750 and 14,215 m³/h at 30%, 70% and 100% speed. The data are for illustration and are manufacturer claims.
Key points
- Over 200 kW sensible cooling in a single rack; three operating points: maximum 204 kW, nominal 177 kW, efficient 164 kW.
- Maximum: 14/20 °C water, 15 °C air off, water flow 29.38 m³/h (8.16 L/s), fluid velocity 4.84 m/s.
- Nominal: 20/30 °C water (wide ΔT), 22.5 °C air off, 15.27 m³/h, 2.51 m/s.
- Efficient: 23/33 °C water, 26 °C air off, 14.2 m³/h, 2.34 m/s; allows free cooling with negligible capacity loss versus nominal.
- All points use 65 °C air-on dry-bulb and 14,229 m³/h airflow (50 Hz, 230 V).
- EER exceeds 100 at maximum duty (manufacturer claim).
- Size: height 2303 (48U) and 2481 mm (52U), width 799 mm, depth 415 mm; dry weight 150 and 163 kg, wet weight 172 and 185 kg.
- Ten backward-curved centrifugal fans: 4,375 m³/h at 30%, 10,750 at 70%, 14,215 at 100%; maximum current 16 A; water volume 22 L; connection 32 mm.
- Communication Modbus over TCP/IP; BACnet and SNMP optional.
Using it in design
- For 200 kW-class dense racks, consider RDHx as an alternative to direct-to-chip and immersion cooling for its ability to keep standard racks and servers and to retrofit.
- Water temperature choice sets capacity: 204 kW at 14/20 °C, 177 kW at 20/30 °C, 164 kW at 23/33 °C; for a free cooling target choose warmer water and wide ΔT.
- Compare the 65 °C air-on assumption with your own server exhaust temperature.
- Check water flow (14.2 to 29.4 m³/h) and fluid velocity up to 4.84 m/s against pipe size, pumps and erosion limits.
- Check the 150 to 185 kg weight and 415 mm depth against rack and floor loading, aisle width and hinge side.
Who should read it
Data center designers and operators applying rear door cooling to HPC and AI racks.
Document contents
- ColdLogik CL23 RDHx introduction
- Performance examples (maximum, nominal, efficient)
- Technical data (48U, 52U)
- Combined fan performance
Publication details
- Authors
- USystems
- Publisher
- Legrand / USystems
- Year
- 2024
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
USystems (2024). ColdLogik CL23 Rear Door Heat Exchanger Data Sheet. Legrand / USystems. https://cdn.prod.website-files.com/65d3dd61583b600eeb976a07/66337935c030ef146d0d8e29_CL23%20Datasheet.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
