Import RD 01-21 as parametric AI-hall templates (rack kW, racks per module, module kW, redundancy of fan walls/TMUs/towers, generator and transformer counts) and as golden test cases for capacity math.
- Power distribution supports 2N, DR and BR architectures.
Eaton / Trane 2025
Reference Design #505: Eaton 1 GW Power Architecture Meets Trane Thermal Management
Voltage-selection rule: motors above about 200 kW (large chillers and pumps) default to MV (4.16/6.6/11 kV) feeders; compute I = P/(sqrt(3) x V x PF) to show cable savings.
- 1,500 HP pump: 1,420 A at 480 V vs 164 A at 4.16 kV
BICSI (via Cabling Installation & Maintenance) 2019
ANSI/BICSI 002-2019, Data Center Design and Implementation Best Practices (release announcement)
Keep BICSI 002 edition history (2014, 2019, 2024) in the standards registry for projects citing older editions.
- Previous edition; superseded by BICSI 002-2024.