Data Center World
About the event
Four-day conference and expo held in association with AFCOM covering data centre planning, power, cooling and operations, aimed at data centre managers and facility professionals.
Who it is for / why attend
For operators, design and construction leaders, energy professionals and investors. It has dedicated Design, Construction & Supply Chain and Power, Cooling & Sustainability tracks, 120+ sessions, an Investor Summit and 600+ exhibitors.
Venue
Dates and details are compiled from official organiser sources. Check the official website for the programme, admission requirements and registration status before making plans.
Read before you go
Explore the libraryHuawei Digital Power 2025
Huawei AI Data Center Reference Design
Import RD 01-21 as parametric AI-hall templates (rack kW, racks per module, module kW, redundancy of fan walls/TMUs/towers, generator and transformer counts) and as golden test cases for capacity math.
- Power distribution supports 2N, DR and BR architectures.
Eaton / Trane 2025
Reference Design #505: Eaton 1 GW Power Architecture Meets Trane Thermal Management
Voltage-selection rule: motors above about 200 kW (large chillers and pumps) default to MV (4.16/6.6/11 kV) feeders; compute I = P/(sqrt(3) x V x PF) to show cable savings.
- 1,500 HP pump: 1,420 A at 480 V vs 164 A at 4.16 kV
BICSI (via Cabling Installation & Maintenance) 2019
ANSI/BICSI 002-2019, Data Center Design and Implementation Best Practices (release announcement)
Keep BICSI 002 edition history (2014, 2019, 2024) in the standards registry for projects citing older editions.
- Previous edition; superseded by BICSI 002-2024.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo