Technical guideFree to read2008

Directional protection and directional zone selectivity

ABB

ABB application paper on the directional (D) protection and directional zone selectivity functions of the PR123/PR333 trip units for LV systems with more than one source.

On this page

Overview

Directional protection D works like a definite-time S function but with two delays, t7FW (forward) and t7BW (backward), applied once threshold I7 is exceeded; it needs no auxiliary supply or dedicated wiring. Direction is decided from reactive power: the phase reactive power must exceed 2% of nominal phase power, otherwise the relay uses the shorter of t7FW and t7BW.

Directional zone selectivity requires zone selectivity S and G to be off and a 24 V DC auxiliary supply; each relay has DFin/DBin inputs and DFout/DBout block outputs. Breakers bounding the faulted section trip at t7s, and if one fails to open the next upstream breaker opens after about a further 100 ms. Without auxiliary power, directional zone selectivity degrades to plain directional protection with t7FW/t7BW times, which the designer must allow for.

The paper shows how lock signals between relays isolate a faulted section in ring or meshed networks. Worked examples cover two generators on a common busbar, a double-transformer substation with bus tie, and a board fed by LV generators in parallel with transformers, followed by a practical commissioning guide.

Key points

  1. D works like a definite-time S with two delays (t7FW forward, t7BW backward) above threshold I7; no auxiliary supply or dedicated wiring needed.
  2. Direction comes from reactive power; phase reactive power must exceed 2% of nominal phase power, otherwise the shorter of t7FW and t7BW is used.
  3. Directional zone selectivity needs S and G zone selectivity off and a 24 V DC auxiliary supply; DFin/DBin inputs and DFout/DBout outputs.
  4. Breakers bounding the faulted section trip at t7s; if one fails, the next upstream opens about 100 ms later.
  5. Without auxiliary power it degrades to plain directional protection with t7FW/t7BW times.
  6. Examples: two generators on one busbar, MV/LV substation with bus tie, LV generators in parallel with transformers.

Using it in design

  • For main switchboards with two transformers plus bus tie, or generator paralleling boards, flag that conventional time selectivity cannot discriminate fault direction and propose directional or directional-zone selectivity on incomers and bus tie.
  • Capture per breaker whether it supports D/ZSI-D and whether auxiliary supply is present.
  • Warn that loss of 24 V DC auxiliary reverts to slower directional times and include that in the selectivity study.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Electrical engineers designing selectivity for multi-source LV boards with parallel transformers or generators.

Related standards

  • IEC 60947-2
  • IEC 60947-1

Publication details

Authors
ABB
Publisher
ABB
Year
2008
Document number
1SDC007401G0201
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

ABB (2008). Directional protection and directional zone selectivity. ABB. 1SDC007401G0201. https://library.e.abb.com/public/c1a005fc597b0df7c1257ac5003d1c59/1SDC007401G0201.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.