Wet Stacking Prevention Technologies for Cat 3500 Diesel Generator Sets

Caterpillar · Roger Rosborough

Caterpillar LEXE20210-00 (Roger Rosborough, 2021) explains wet stacking on diesel generator sets run for long periods at light load, and the engine features Cat uses on 3500 Series units to mitigate it. It applies to data-centre gensets routinely exercised unloaded or lightly loaded.

On this page

Overview

Wet stacking arises from extended operation at low load (under 30%) and shows as black liquid at exhaust joints. Prolonged under-loading also accelerates component wear, with further detail left to white paper LEXE0832.

The mitigations split into hardware and software. Hardware means piston-ring and oil-scraping design and exhaust valve stem seals. The two software strategies disable injectors so the firing cylinders stay hot.

Cold Cylinder Cutout (CCC) switches off one unit injector at a time during cold start and extended low load. Idle Cylinder Cutout (ICC) cuts several injectors in sequence at rated speed when load is between 0% and an engine-specific limit, typically about 10-25%. If both sets of conditions are met, CCC takes priority, and either strategy deactivates immediately when a parameter leaves its range.

Key points

  1. Wet stacking comes from extended operation below 30% load and appears as black liquid at exhaust joints.
  2. Prolonged under-loading accelerates component wear (see LEXE0832).
  3. Hardware measures: piston-ring/oil-scraping design and exhaust valve stem seals.
  4. Cold Cylinder Cutout turns off one injector at a time during cold start and extended low load.
  5. Idle Cylinder Cutout cuts multiple injectors in sequence at rated speed between 0% load and an engine-specific limit of about 10-25%.
  6. When both conditions are met, CCC takes priority.

Using it in design

  • Warn when planned monthly exercise or normal running load is under 30% of rating, and recommend load-bank testing or a reduced set count.
  • Add a low-load mitigation field (cylinder cutout) to the generator catalog.
  • Include periodic load-bank runs in commissioning templates for lightly loaded data-centre gensets.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Operations and design engineers planning testing, maintenance and commissioning of data-centre generators.

Related standards

  • NFPA 110

Publication details

Authors
Roger Rosborough
Publisher
Caterpillar
Year
2021
Document number
LEXE20210-00
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Roger Rosborough (2021). Wet Stacking Prevention Technologies for Cat 3500 Diesel Generator Sets. Caterpillar. LEXE20210-00. https://www.finning.com/content/dam/finning/en_gb/Documents/Industries/ElectricPower/cat-white-papers-march-2024/Wet%20Stacking%20Prevention%20Technologies%20for%20Cat%C2%AE%203500%20Diesel%20Generator%20Sets%20(LEXE20210-00).pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.