Alternator winding pitch and power system design
Cummins · Rich Scroggins, David Matuseski
Cummins Power Topic #5981 (Rich Scroggins and David Matuseski, 2014) explains how alternator winding pitch shapes harmonic content and how to choose between 2/3 and 5/6 pitch. It yields a direct rule for four-wire low-voltage systems in data centres.
On this page
Overview
The paper defines pitch factor as Kp = cos(N x 180 x (1 - pitch)/2), with N the harmonic order. Table 1 gives Kp for 2/3 pitch as 0.87 at the fundamental, 0.00 at the 3rd and 0.87 at the 5th and 7th; for 5/6 pitch the values are 0.97, 0.71, 0.26 and 0.26. A 2/3 pitch winding therefore generates no triplen harmonics (3rd, 9th, 15th, 21st).
The conclusion is a selection rule: 2/3 pitch for all four-wire distribution systems, and 5/6 pitch where no neutral is distributed, typical of MV and HV plants. The trade-off is capacity: a 5/6 pitch winding yields about 97% of full-pitch fundamental voltage against about 87% for 2/3, so it extracts more kVA from the same frame.
The final part covers paralleling alternators of different pitch. It is allowed provided circulating neutral current is mitigated, with reactors or resistors in the neutral leg or neutral switching; Figures 8-11 show these arrangements.
Key points
- Pitch factor: Kp = cos(N x 180 x (1 - pitch)/2).
- 2/3 pitch Kp: fundamental 0.87, 3rd 0.00, 5th and 7th 0.87.
- 5/6 pitch Kp: 0.97, 0.71, 0.26, 0.26.
- 2/3 pitch produces no triplen harmonics (3rd, 9th, 15th, 21st).
- Recommendation: 2/3 pitch on all 4-wire systems; 5/6 acceptable without a distributed neutral (most MV/HV).
- 5/6 pitch gives about 97% fundamental voltage versus about 87% for 2/3, hence more kVA per frame.
- Different-pitch alternators can be paralleled if circulating neutral current is handled by neutral reactors or neutral switching.
Using it in design
- Add a windingPitch field to the alternator catalog and require 2/3 pitch (or flag) for LV 4-wire generator systems.
- When sets of different pitch with bonded neutrals are paralleled, raise a warning and suggest a neutral reactor or 3-pole isolation.
- Accept 5/6 pitch for MV plants with delta transformer primaries.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Electrical engineers specifying generators and alternators, especially for four-wire LV standby systems.
Related standards
- IEC 60034-1
- NEMA MG 1
Publication details
- Authors
- Rich Scroggins; David Matuseski
- Publisher
- Cummins
- Year
- 2014
- Document number
- Power Topic #5981
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Rich Scroggins; David Matuseski (2014). Alternator winding pitch and power system design. Cummins. Power Topic #5981. https://mart.cummins.com/imagelibrary/data/assetfiles/0056601.pdf