RegulationFree to read2014

Electricity Grid Regulation (Elektrik Şebeke Yönetmeliği)

Original title Elektrik Şebeke Yönetmeliği

Enerji Piyasası Düzenleme Kurumu (EPDK)

The Turkish transmission grid code setting planning, operation, supply reliability and power-quality conditions for users connected to TEİAŞ's network.

On this page

Overview

The Electricity Grid Regulation was issued by the Energy Market Regulatory Authority (EPDK) and published in Official Gazette 29013 (repeated issue) of 28.05.2014. It is the Turkish transmission grid code, governing planning, operation, supply reliability and power-quality conditions for users connected to the TEİAŞ network. Data centres connected at 154 kV or fed from TEİAŞ substations must comply with its harmonic and reactive energy limits.

The regulation defines the grid quantities. Nominal frequency is 50 Hz, controlled by TEİAŞ within 49.8-50.2 Hz. Nominal transmission voltages are 400, 154 and 66 kV; normal operating bands are 340-420 kV and 140-170 kV, and plus or minus 10% for 66 kV and below. Distribution-level voltages inside the transmission system are listed as 34.5, 33, 31.5, 15.8, 10.5 and 6.3 kV.

On power quality, users connected to the transmission system must respect the current harmonic limits in Annex 8 at the point of common coupling. Monthly inductive reactive energy may not exceed 20% of the active energy drawn, and capacitive reactive energy fed back may not exceed 15%. In 400 kV and 154 kV systems, negative-sequence voltage should not exceed 1% of positive sequence. N-1 planning also falls within the regulation's scope.

As a limitation, this summary rests only on the recorded articles; the detail of the Annex 8 harmonic tables is not reproduced here.

Key points

  1. Nominal frequency is 50 Hz, controlled by TEİAŞ within 49.8-50.2 Hz (Article 7).
  2. Nominal transmission voltages are 400, 154 and 66 kV; operating bands 340-420 kV and 140-170 kV, plus or minus 10% for 66 kV and below (Article 8).
  3. Distribution-level voltages inside the transmission system: 34.5, 33, 31.5, 15.8, 10.5 and 6.3 kV (Article 8).
  4. Users connected to transmission must respect the Annex 8 current harmonic limits at the point of common coupling (Article 13).
  5. Monthly inductive reactive energy may not exceed 20% of active energy, and capacitive reactive energy 15% (Article 14).
  6. Negative-sequence voltage in 400 kV and 154 kV systems should not exceed 1% of positive sequence (Article 23).
  7. Data centres connected at 154 kV or fed from TEİAŞ substations are subject to the harmonic and reactive limits.

Using it in design

  • In power-quality checks, assess harmonic current emission of UPS and IT loads against Annex 8 limits at the point of common coupling, and size active filters if needed.
  • Size power-factor correction so that monthly inductive and capacitive reactive ratios stay below 20% and 15%.
  • Use 34.5 kV and 154 kV as the default voltage options for large sites.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Electrical designers and grid-connection leads for data centres connecting to the TEİAŞ network.

Related standards

  • Elektrik Piyasası Bağlantı ve Sistem Kullanım Yönetmeliği
  • IEC 61000-3-12
  • IEEE 519

Publication details

Authors
Enerji Piyasası Düzenleme Kurumu (EPDK)
Publisher
Enerji Piyasası Düzenleme Kurumu (EPDK)
Year
2014
Document number
RG 29013 mükerrer (28.05.2014)
Document language
Turkish
Source type
Turkish regulation
Access
Free to read
Licence
Bibliographic reference only — the document is not redistributed here; confirm reuse terms at the original source
Original licence note

Official Turkish legislation published in the Resmî Gazete; FSEK (Law 5846) Art. 31 makes laws and regulations freely reproducible, but this library keeps it citation-only by policy. Text read from mevzuat.gov.tr (consolidated version as of 2026-11).

Citation

Enerji Piyasası Düzenleme Kurumu (EPDK) (2014). Elektrik Şebeke Yönetmeliği. Enerji Piyasası Düzenleme Kurumu (EPDK). RG 29013 mükerrer (28.05.2014). https://www.mevzuat.gov.tr/mevzuat?MevzuatNo=19722&MevzuatTur=7&MevzuatTertip=5

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.