Technical guideFree to read2025

Meeting the Demands of Flexible Data Center Design

Legrand

Legrand argues that flexibility is the design principle that best supports change over a data centre's life, and applies it to the cabinet and the rack PDU. Its main concern is why PDU mounting brackets so often delay installations.

On this page

Overview

The paper states that racks are often replaced at refresh because they cannot accommodate new equipment form factors, and that cabinets carry thousands of pounds of equipment on footprints as small as 600 mm x 1000 mm. These two observations frame cabinet and PDU choice as a lifecycle decision.

On the electrical side, busway and three-phase rack PDUs with alternating-phase and combination outlets are presented as flexible infrastructure that lets racks be repopulated. Combination C13/C19 outlets accept both C14 and C20 plugs, easing future IT refreshes, and the alternating-phase layout supports three-phase balancing. Intelligent rack PDUs can shed non-critical loads in a predefined priority order on main-source failure.

The weight of the paper is on mounting. PDU brackets are described as a frequent cause of installation delay, and five common configurations are listed: single facing inside, double facing inside, single facing outside, double facing outside and quadruple facing inside. The remedy offered is toolless, vertically adjustable PDU mounting in the cabinet frame. As a vendor white paper, the remedy points to Legrand's own approach and gives no comparative numeric data.

Key points

  1. Combination C13/C19 outlets accept both C14 and C20 plugs, easing IT refreshes.
  2. Alternating-phase outlet layout supports three-phase balancing.
  3. Intelligent rack PDUs can shed non-critical loads in a predefined priority order when the main source fails.
  4. Cabinets carry thousands of pounds of equipment on footprints as small as 600 mm x 1000 mm.
  5. Five common PDU configurations: single/double facing inside, single/double facing outside, quadruple facing inside.
  6. Racks are often replaced at refresh because they cannot take new equipment form factors.

Using it in design

  • In the cabinet catalogue record supported PDU mounting positions (count, inside/outside, 0U slots) and whether mounting is toolless.
  • Raise an error when a design specifies more PDUs per cabinet than the supported positions, and carry PDU brackets as BOM line items.
  • Prefer combination outlets in outlet planning when the future IT refresh mix is unknown.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Designers choosing cabinets and rack PDUs with refresh cycles in mind.

Related standards

  • IEC 60320

Publication details

Authors
Legrand
Publisher
Legrand
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Legrand (2025). Meeting the Demands of Flexible Data Center Design. Legrand. https://legrand.com/datacenter/sites/g/files/ocwmcr716/files/2025-05/White%20Papers%20-%20Meeting%20the%20Demands%20of%20Flexible%20Data%20Center%20Design.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.