Cooling Options for Rack Equipment with Side-to-Side Airflow
Schneider Electric · Neil Rasmussen
Neil Rasmussen's paper explains why switches and routers that draw air in one side and exhaust it out the other clash with hot-aisle/cold-aisle rooms built for front-to-back equipment, and compares four ways to cope.
On this page
Overview
The problem comes from three recirculation mechanisms: adjacent equipment feeding its exhaust into the next intake, no partition between intake and exhaust, and enclosures amplifying the effect. In open-frame rows, the intake air of side-breathing equipment can run 10°C (18°F) above ambient because of neighbouring exhaust, and the excess grows rack by rack along the row. Under MIL-HDBK 338, every 10°C above nominal halves equipment lifetime.
Four mitigations are compared on density, floor space, efficiency, predictability and TCO: spaced open frames, low-density enclosures, supplemental fans, and active side air distribution that converts the flow to front-to-back. Rack density limits are 0-1 kW, 0-1 kW, 0-2 kW and 0-6 kW respectively. In a test with a Cisco 6500 switch in a 42U enclosure, rack side air distribution lowered switch inlet temperature by an average of 8.3°C (15°F).
The paper also collects reference limits and vendor restrictions: the ANSI T1.304-1997 telecom operating range of 5 to 40°C, the ASHRAE TC9 recommended inlet of 18 to 27°C, and shutdown of side-breathing equipment above 40°C. Vendor guidelines call for at least 6 inches between a wall and chassis vents and 12 inches between two chassis. Recirculation is said to add over 10% to CRAC electricity cost. The 2011 study predates current product-level side-airflow solutions.
Key points
- Per MIL-HDBK 338, every 10°C (18°F) rise above nominal temperature halves equipment lifetime.
- In open-frame rows, side-to-side equipment intake air may be 10°C (18°F) above ambient because of adjacent exhaust, and it accumulates along the row.
- Recirculation and hot spots can raise CRAC electricity cost by over 10%; cooling often takes nearly half of data-centre electricity.
- Test in a 42U enclosure with a Cisco 6500: side air distribution lowered inlet temperature by an average of 8.3°C (15°F).
- Density per rack: spaced open frames 0-1 kW, low-density enclosure 0-1 kW, supplemental fan 0-2 kW, side air distribution 0-6 kW.
- Quoted limits: ANSI T1.304 range 5-40°C, ASHRAE TC9 recommended inlet 18-27°C; side-breathing gear typically shuts down above 40°C.
- Vendor restrictions: at least 6 inches wall-to-vent, 12 inches between chassis horizontally, no congested or unventilated enclosed racks, use baffles.
Using it in design
- Add an airflowPattern field to the equipment catalogue (front_to_back, back_to_front, side_to_side, side_to_back) and fill it in for switches and routers first.
- Warn when a side_to_side device sits in an enclosed rack with no side-air-distribution or baffle accessory; cap rack density near 1 kW (open/spaced) or 2 kW (fans) unless such a unit is specified, which allows up to 6 kW.
- Flag adjacent racks where side exhaust lines up with the neighbour's intake; without ducting, reserve U space for air-turning devices and keep 6 inches to walls and 12 inches between chassis.
- Show the 10°C-halves-life rule next to inlet-temperature risk in reliability tooltips.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Designers placing switches, routers and other side-breathing gear in network rooms and data-centre halls.
Related standards
- ASHRAE TC 9.9 Thermal Guidelines
- ANSI T1.304
- EIA-310-D
- MIL-HDBK-338
Publication details
- Authors
- Neil Rasmussen
- Publisher
- Schneider Electric
- Year
- 2011
- Document number
- WP 50
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Neil Rasmussen (2011). Cooling Options for Rack Equipment with Side-to-Side Airflow. Schneider Electric. WP 50. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_SADE-5TNRKJ_EN
Events on this subject
- ISK-SODEX Istanbul 2027
- SC26 – International Conference for High Performance Computing, Networking, Storage and Analysis
- ASHRAE Winter Conference
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.