White paperFree to read2022

Environmental Sustainability Management (ESM) Software for Colocation Data Centers

Schneider Electric · Patrick Donovan

Patrick Donovan argues that colocation operators need a dedicated sustainability management platform as a fourth pillar next to BMS, EPMS and DCIM.

On this page

Overview

The paper positions ESM as the fourth pillar of data-centre management: BMS for mechanical and electrical systems, DCIM for the physical infrastructure of the IT space, EPMS for electrical distribution metering. The driver is regulatory and investor pressure: over 40 countries require GHG reporting, and a provider's Scope 1 and 2 emissions are a significant source of tenants' Scope 3. In a cited survey, 80% of C-level executives struggle with coordinated sustainability planning, 59% lack a global view of data and only 12% of collected data is used.

The platform has four core functions: capture data, harmonise and validate it, analyse it, and support decisions and reporting. The second must normalise across units, time zones, currencies, languages and polling intervals and flag gross outliers for manual review. Five desirable attributes include cloud delivery, invoice-management services and support for frameworks such as GRESB. Those metrics include PUE, REF and ERF for energy, WUE for water and CUE for emissions, so the platform data model must carry quantities beyond kWh, such as m3 and kg CO2e.

The paper reproduces the 23-metric set from WP 67: energy 5, GHG 9, water 4, waste 4, land and biodiversity 1, with recommended counts of 11, 18 and 23 for beginning, advanced and leading maturity. Its design value is in defining which metrics and metering points a new facility should report from day one; sub-meters linking tenant spaces to IT-space meters or DCIM data support auditable billing and can supply tenants with Scope 3 data.

Key points

  1. ESM is the 4th pillar beside BMS (mechanical/electrical), DCIM (IT-space physical infrastructure) and EPMS (electrical distribution metering).
  2. Over 40 countries require GHG reporting; a provider's Scope 1 and 2 emissions are a significant source of tenants' Scope 3.
  3. Cited survey: 80% of C-level executives struggle with coordinated planning, 59% lack a global data view, only 12% of collected data is used.
  4. 23 metrics in 5 categories: energy (5), GHG (9), water (4), waste (4), land and biodiversity (1); recommended counts are 11 beginning, 18 advanced, 23 leading.
  5. Energy metrics include total kWh, PUE, renewable kWh, REF and ERF; water metrics total site water (m3) and WUE (m3/kWh); GHG metrics location- and market-based Scope 2 and CUE.
  6. The platform must normalise units, time zones, currencies, languages and polling intervals, and flag gross outliers for manual review.
  7. Sub-metering that links IT-space meters or DCIM data to tenant spaces enables auditable billing and can supply tenants with Scope 3 data.

Using it in design

  • In the metering plan generator, confirm meters exist to produce the chosen maturity tier's metric set: total facility kWh, IT kWh for PUE, renewable kWh, site water m3 for WUE, reused energy for ERF.
  • Add per-tenant sub-metering points to colocation layouts.
  • Tag catalogue meters with measured quantity and unit, and flag designs where WUE or ERF cannot be computed.
  • Export metrics with units and maturity-tier labels, and use a tooltip to distinguish location-based from market-based Scope 2.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Compare the cost of design decisions

Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.

Request a demo
CAPEX and TCO estimates in the SoSo CAD cost workspace

Who should read it

Colocation operators and designers planning the metering and reporting backbone of a new facility.

Related standards

  • ISO/IEC 30134-2
  • ISO/IEC 30134-8
  • ISO/IEC 30134-9
  • GHG Protocol

Publication details

Authors
Patrick Donovan
Publisher
Schneider Electric
Year
2022
Document number
WP 54
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Patrick Donovan (2022). Environmental Sustainability Management (ESM) Software for Colocation Data Centers. Schneider Electric. WP 54. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP54_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.