White paperFree to read2021

Gas-insulated, arc-resistant switchgear for critical power applications (white paper)

Siemens

A Siemens Industry (US) white paper comparing air-insulated (AIS) and gas-insulated (GIS) medium-voltage switchgear for data-centre substations, arguing the case for GIS on maintenance, failure causes, safety and floor space.

On this page

Overview

The paper argues that GIS with vacuum interrupters and SF6 insulation reduces maintenance, removes environment-driven failure modes and improves operator safety through arc-resistant design. It is a manufacturer publication, so it is an advocacy piece listing the advantages of one product class rather than a neutral comparison, and its claims should be read that way.

The floor-space figures are the most concrete claim: compared with air-insulated switchgear, GIS saves on average more than 50% of footprint for systems up to 15 kV and more than 75% up to 38 kV. The other listed benefits are a 10-year inspection interval, an isolated-phase design that removes phase-to-phase faults, and arc-resistance tested to ANSI/IEEE C37.20.7.

The reliability argument rests on IEEE 493 (Gold Book) failure-cause data. For AIS, moisture accounts for 30% of failure causes, protective-device malfunction 10%, dust and contaminants 10% and ageing 10%. The paper estimates that about 50% of failure causes do not apply to sealed MV GIS. This is an inference from the cause distribution, not a measured failure rate.

The closing section says the highest-reliability data-centre substations should accept utility power from at least two sources, with automatic switching and interlocking. It adds that isolated-phase GIS lineups can be extended without interrupting supply to connected load.

Key points

  1. GIS footprint savings average over 50% for systems up to 15 kV and over 75% up to 38 kV versus AIS.
  2. Claimed benefits: 10-year inspection interval, isolated-phase design removing phase-to-phase faults, arc resistance tested to ANSI/IEEE C37.20.7.
  3. IEEE 493 AIS failure causes: moisture 30%, protective-device malfunction 10%, dust/contaminants 10%, ageing 10%.
  4. An estimated 50% of AIS failure causes do not apply to MV GIS.
  5. Highest-reliability substations should take utility power from at least two sources with automatic switching and interlocking.
  6. Isolated-phase GIS lineups can be extended without interrupting supply to connected load.

Using it in design

  • In the MV switchgear catalogue store insulation {AIS, GIS}, arc-resistance standard and rating, inspection interval and footprint.
  • Apply the paper's footprint factors in the space planner when GIS is selected.
  • Let the reliability model use lower failure-rate assumptions for sealed GIS, citing the IEEE 493 cause categories.
  • For Tier III/IV targets, require two utility incomers with automatic transfer at the MV substation.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Electrical designers and decision makers choosing between AIS and GIS for a data-centre substation.

Related standards

  • IEEE C37.20.7
  • IEEE 493
  • IEEE C37.20.2

Publication details

Authors
Siemens
Publisher
Siemens
Year
2021
Document number
SIDS-T40117-00-4AUS
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Siemens (2021). Gas-insulated, arc-resistant switchgear for critical power applications (white paper). Siemens. SIDS-T40117-00-4AUS. https://assets.new.siemens.com/siemens/assets/api/uuid:3e50415f-2ab8-4f0d-876a-5552ca7d9b5b/ansi-mv-gis-advantages-paper-en.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.