Technical guideFree to read2020

Energy data and energy for data centers - now and in the future: SIVACON 8PS LData busbar trunking system

Siemens

A product data brochure for Siemens' LData busbar trunking, aimed at high-density data halls fed at 1,000 A or more.

On this page

Overview

LData runs as a busbar line over the racks with plug-in tap-off units. The units can be fitted anywhere along the run except the terminal point, without a fixed grid, for example every 60 cm to suit rack width. A two-stage mounting allows safe live insertion, and an option caps losses below the IEC limits.

The system data: rated current 1,000-2,500 A, Ue 600 V AC, IP21, aluminium conductors, design-verified to IEC 61439-1/-6. The 1,000-2,250 A versions are rated Ipk 84 kA and Icw (1 s) 40 kA, with 2,500 A on request. Fire load is 3.60-4.38 kWh/m by rating, maximum support distance 3 m, weight 20-31 kg/m.

At 415 V the cubic tap-off units go up to 250 A and the L-shaped ones up to 125 A. Tap-off metering data can be sent by powerline communication over the busbar with no extra control wiring, which supports ISO 50001 energy management.

This is a product brochure, so it supplies values and dimension tables rather than a design method. The check that matters in use is comparing the busway's Icw/Ipk with the prospective fault level at the feeding board.

Key points

  1. Rated currents 1,000-2,500 A, Ue 600 V AC, IP21, aluminium conductors, design-verified to IEC 61439-1/-6.
  2. Ipk 84 kA and Icw (1 s) 40 kA for the 1,000-2,250 A versions; 2,500 A on request.
  3. Fire load 3.60-4.38 kWh/m, maximum support distance 3 m, weight 20-31 kg/m.
  4. Tap-off units fit anywhere except the terminal point without a fixed grid (e.g. every 60 cm to suit rack width).
  5. At 415 V cubic units go up to 250 A, L-shaped up to 125 A.
  6. Tap-off metering data travels by powerline over the busbar with no extra control wiring, supporting ISO 50001.

Using it in design

  • Check busway Icw/Ipk against the prospective fault level at the feeding board.
  • Compute fire load per metre as an input to the fire strategy.
  • Let the rack-row layout place tap-offs at rack pitch.
  • Provide per-tap-off energy metering points for PUE and rack billing.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Electrical designers selecting rack-feed busway for high-density data halls.

Related standards

  • IEC 61439-1
  • IEC 61439-6
  • ISO 50001

Publication details

Authors
Siemens
Publisher
Siemens
Year
2020
Document number
SIDS-B10022-00
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Siemens (2020). Energy data and energy for data centers - now and in the future: SIVACON 8PS LData busbar trunking system. Siemens. SIDS-B10022-00. https://assets.new.siemens.com/siemens/assets/api/uuid:e276a0b7-a825-4a92-9cc0-c488400c734f/sids-b10022-00dbldatasivacon8psenus-144.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.