Evaluation and Optimization of a Two-Phase Liquid-Immersion Cooling System for Data Centers
Energies (MDPI AG) · Cheng Liu, Hang Yu
Tongji University researchers tested a lab two-phase immersion system in which servers sit in Novec 7100 that boils and condenses against an external heat-exchanger loop, measuring cooling COP, partial PUE and exergy efficiency at server powers of about 1.1-1.6 kW.
CC BY 4.0 — share with attribution
On this page
Overview
The study starts from the premise that an efficient cooling system for data centres can boost server working efficiency and promote energy savings, and explores the performance of a two-phase cooling system with a laboratory experiment and CFD simulation. The working fluid is Novec 7100. The COP and partial PUE (pPUE) were evaluated under various IT loads; the relationship between the interval of submerged servers and their surface temperatures was then evaluated by CFD to obtain the minimum intervals keeping server surfaces below 85 °C.
As server power rose from 1127 W to 1577 W, system COP increased from 19.0 to 26.7, generally 4-20 units higher than reported air- or water-cooled systems. The pPUE of the two-phase system fell from 1.053 to 1.037 as server power increased. Exergy efficiency ranged from 12.65% to 18.96% (average 14.84%), with most exergy destruction on the tank side. COP and PUE depended on room temperature and on the fan and pump speed of the external heat exchanger.
To keep server surfaces below 85 °C, server spacing must be at least 15 mm at 1000 W and 20 mm at 1500 W; at 2000 W or 3000 W even 30 mm was insufficient. For a given tank, a closer interval between servers causes higher server surface temperature, and the allowable board pitch grows quickly with per-server power.
Limits: a single laboratory system, one fluid (Novec 7100) and a 1.1-1.6 kW experimental range; spacings above 2000 W were predicted by CFD. Results depend on tank geometry and the external heat-exchanger setting.
Key points
- As server power rose from 1127 W to 1577 W, system COP increased from 19.0 to 26.7, generally 4-20 units higher than reported air- or water-cooled systems.
- The pPUE of the two-phase system fell from 1.053 to 1.037 as server power increased.
- Exergy efficiency ranged from 12.65% to 18.96% (average 14.84%), with most exergy destruction on the tank side.
- To keep server surfaces below 85 °C, server spacing must be at least 15 mm at 1000 W and 20 mm at 1500 W; at 2000 W or 3000 W even 30 mm was insufficient.
- COP and PUE depended on room temperature and on the fan and pump speed of the external heat exchanger.
- The working fluid was Novec 7100.
Using it in design
- In a two-phase immersion tank, set server spacing by power: at least 15 mm at 1000 W and 20 mm at 1500 W for the 85 °C surface limit, and wider for 2000 W and above.
- Report efficiency (COP 19-26.7, pPUE 1.037-1.053) by IT load; efficiency improved as load rose, so do not expect design-point values at low load.
- Manage the external heat exchanger's fan and pump speed and room temperature as control variables for COP and PUE.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Cooling engineers designing two-phase immersion tanks and server spacing.
Document contents
- 1. Introduction
- 2. Methodology (2.1 Experimental Study, 2.2 CFD Simulation: physical model and boundary conditions, CFD modeling of boiling flow, material properties, grid independence, CFD model validation; 2.3 COP and pPUE, 2.4 Exergy Analysis)
- 3. Results and Discussion (3.1 COP and pPUE, 3.2 Exergy Analysis, 3.3 Simulation Results)
- 4. Conclusions
Read the document
two-phase-immersion-evaluation-optimization-2021.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Cheng Liu; Hang Yu
- Publisher
- Energies (MDPI AG)
- Year
- 2021
- Volume
- 14
- Issue
- 5
- Pages
- 1395
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1 states the article is open access under the Creative Commons Attribution (CC BY 4.0) licence; MDPI publishes all articles under CC BY 4.0.
Citation
Cheng Liu; Hang Yu (2021). Evaluation and Optimization of a Two-Phase Liquid-Immersion Cooling System for Data Centers. Energies (MDPI AG). 14(5), 1395. https://doi.org/10.3390/en14051395
Events on this subject
- SC26 – International Conference for High Performance Computing, Networking, Storage and Analysis
- NVIDIA GTC
- ISC High Performance
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.