Uptime Institute Global Data Center Survey 2022 (12th annual) - press release
Uptime Institute · Uptime Institute, J. Davis et al.
Press release for Uptime Institute's twelfth annual survey of about 800 owners/operators and 700 suppliers, summarising the state of PUE, redundancy, outage cost, sustainability reporting and staffing.
On this page
Overview
This document is the press release for Uptime Institute's twelfth annual global data center survey, run in the first half of 2022. About 800 data center owners and operators took part, together with 700 suppliers. The release highlights a handful of headline findings that indicate where the industry is heading: average PUE, investment in redundancy, outage costs, readiness for environmental reporting and the difficulty of finding qualified staff.
On energy efficiency, the average annual PUE was reported as 1.55 in 2022, slightly below the 1.57 recorded in 2021. There is therefore no dramatic jump in efficiency; improvement remains slow. On resiliency, about 40% of respondents said they had raised redundancy levels at their primary data centers over the previous three to five years. Read together, the two findings suggest operators are more willing to add capacity for continuity than to chase efficiency gains.
The outage findings are the most frequently quoted part of the release. The share of respondents reporting an outage in the past three years fell to 60%, down from 69% in 2021 and 78% in 2020. Yet the share of outages costing more than $1 million rose from 15% to 25%, and more than two-thirds of outages cost over $100,000. Outages are becoming less frequent but more expensive.
The sustainability and workforce findings point to a readiness gap. Only 37% of respondents collect and report carbon emissions and 39% report water use. Those reporting difficulty finding qualified staff rose to 53%, from 38% in 2018.
Key points
- Average annual PUE was 1.55 in 2022 versus 1.57 in 2021.
- About 40% raised redundancy levels at primary data centers in the past three to five years.
- Outages costing over $1 million reached 25% of the total (15% in 2021); more than two-thirds cost over $100,000.
- 60% reported an outage in the past three years (69% in 2021, 78% in 2020).
- Only 37% collect and report carbon emissions; 39% report water use.
- 53% report difficulty finding qualified staff (38% in 2018).
- Survey ran in H1 2022 with about 800 owners/operators and 700 suppliers.
Using it in design
- Use the outage-cost distribution to justify redundancy upgrades: over $100,000 is common and over $1 million occurs in roughly one in four to five outages.
- In the cost module, compare the expected cost of an outage with the capital cost of the proposed redundancy increase.
- Benchmark PUE targets against the 1.55 industry average to set a realistic reference line.
- Plan metering and sub-metering at design stage to support carbon and water reporting, since most of the industry does not yet report.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Assess redundancy through scenarios
Compare normal operation and equipment failures in SoSo CAD, with supplied loads and capacity shortfalls in one view.
Request a demo
Who should read it
Data center investors, operations managers and design engineers preparing a redundancy or investment case.
Publication details
- Authors
- Uptime Institute; J. Davis; D. Bizo; A. Lawrence
- Publisher
- Uptime Institute
- Year
- 2022
- Document language
- English
- Source type
- Industry body
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Original licence note
Publisher press release / public web page; copyright Uptime Institute, no open licence. Citation only.
Citation
Uptime Institute; J. Davis; D. Bizo; A. Lawrence (2022). Uptime Institute Global Data Center Survey 2022 (12th annual) - press release. Uptime Institute. https://uptimeinstitute.com/about-ui/press-releases/2022-global-data-center-survey-reveals-strong-industry-growth
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.