Explaining the Uptime Institute's Tier Classification System (April 2021 update)

Uptime Institute Journal · Matt Stansberry

Matt Stansberry's Uptime Journal explainer that corrects common misreadings of the Tier system. Its most important clarification: Tier levels carry no expected downtime or availability percentage.

On this page

Overview

The article first restates the four Tier outcomes. Tier I includes UPS, dedicated cooling and an engine generator; Tier II adds redundant UPS modules, chillers and pumps, and generators. The author stresses that the standard states desired results rather than a prescriptive checklist, so different engineering solutions can reach the same Tier. A separate paragraph handles the most misunderstood point: Uptime removed 'expected downtime per year' and availability percentages from the Tier Standard in 2009, and the current standard assigns no availability predictions to Tiers.

The 99.671 / 99.741 / 99.982 / 99.995 figures still circulating in the market should therefore not be presented as Tier properties. The certification sequence is described as TCDD, TCCF and TCOS. In TCDD Uptime reviews 100% of the design documents. For TCCF, the article reports Uptime's observation that more than 85% of data centre designs are incorrectly executed in construction; the stage ends with a complete 'pull the plug' test. The TCOS paragraph spotlights human error: in the 2021 outage survey (about 1,000 operators) it accounted for more than 70% of downtime, and over 75% of operators said their latest outage was preventable.

This is Uptime describing its own system; the numbers rest on its survey and certification observations and carry no independent verification. Even so, the product conclusion is clear: present a Tier as a verified level of topology and operations, not as an availability promise. The article ties the existence of TCCF after TCDD to an observation: even though design review covers 100% of documents, more than 85% of designs are incorrectly executed in construction, so approval on paper does not guarantee the result on site.

Key points

  1. Uptime removed expected annual downtime / availability percentages from the Tier Standard in 2009; the current standard assigns Tiers no availability predictions
  2. In TCDD Uptime reviews 100% of design documents
  3. Uptime observes more than 85% of data centre designs are incorrectly executed in construction
  4. Human error accounted for more than 70% of downtime; over 75% of operators said their latest outage was preventable (2021 survey, about 1,000 operators)
  5. TCCF ends with a complete 'pull the plug' test
  6. Tier I: UPS, dedicated cooling, engine generator; Tier II adds redundant UPS modules, chillers/pumps and generators

Using it in design

  • Do not display legacy availability percentages such as 99.671/99.741/99.982/99.995 as Tier properties
  • If the app shows availability, compute it from component reliability (RBD/Markov) and label it a model estimate
  • Add an as-built versus design diff nudge in the commissioning module
  • Weight operational readiness heavily in risk scoring

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Assess redundancy through scenarios

Compare normal operation and equipment failures in SoSo CAD, with supplied loads and capacity shortfalls in one view.

Request a demo
Normal operation and failure scenario comparison in SoSo CAD

Who should read it

Consultants who explain Tier terms to clients, product teams, and owners new to certification.

Related standards

  • Uptime Tier Standard: Topology
  • Uptime Tier Standard: Operational Sustainability

Publication details

Authors
Matt Stansberry
Publisher
Uptime Institute Journal
Year
2021
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Matt Stansberry (2021). Explaining the Uptime Institute's Tier Classification System (April 2021 update). Uptime Institute Journal. https://journal.uptimeinstitute.com/explaining-uptime-institutes-tier-classification-system/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.