Alimar Generator Operation and Installation Manual
Original title Alimar Jeneratör Kullanım Kılavuzu
Alimar Jeneratör
Alimar's diesel generator manual sets the room air outlet at no less than 1.5 times the radiator area, a 200-300 mm concrete plinth and exhaust back-pressure rules.
On this page
Overview
The manual brings the safe use, siting, installation, periodic maintenance, panel operation and fault finding of Alimar Jeneratör sets into one document. The manufacturer states that the sets are built to the requirements of TS ISO 8528-4, 8528-5 and 8528-8 and to CE norms. The document has 10 main sections over roughly 64 pages.
For a designer the most useful part is the section on storage, lifting, siting and installation. For the generator room it gives rules such as at least 1 m of working space beside the set, wide outward-opening doors, protection from corrosive or conductive dust, and no shared exhaust duct for multi-generator installations. The set stands on a concrete plinth that carries its weight and vibration; the plinth design is the structural engineer's responsibility.
The ventilation rules centre on the radiator air path: discharge and inlet openings must be at least 1.5 times the radiator area, discharged air must not return to the room, and a sealed flexible bellows connection must join the radiator frame and the discharge opening. Louvres must be L-section and manually operated systems must not be used. On the exhaust side the manual covers back pressure, pipe routing and separation from the clean-air inlet.
As a manufacturer's manual it does not give a calculated airflow method; it refers to capacity tables and to a separate total air requirement table for remote-radiator systems. The maintenance programme is split into daily, 50 h, 250 h or 6 months, 500 h or 1 year, and 1000 h or 2 years. The warranty runs 2 years or 1000 hours from commissioning.
Key points
- Air discharge and inlet openings must be at least 1.5 times the radiator area; the opening must not be blocked and a louvre duct must not be smaller than the discharge cross-section.
- A sealed bellows connection must join the radiator frame and the discharge opening so hot air does not return to the generator room.
- A wind-break barrier is recommended depending on wind direction; its distance must be at least the radiator width.
- The concrete plinth should be 200-300 mm high and raised further where standing water is possible; its design belongs to the structural engineer.
- At least 1 m of working space is left beside the set, and a single exhaust duct must not serve several generators.
- Exhaust bends of 90 degrees need a radius of 3 times the pipe diameter; high back pressure causes excess fuel consumption and high exhaust temperature.
- Exhaust runs should be on sliding supports, with the turbocharger and outlet elbow weight carried by hangers, and the silencer and pipework thermally insulated.
- Noise at 7 m is given as 100-110 dB for unattenuated sets and 70-80 dB for sound-attenuated sets.
- Maintenance intervals are first 50 h, 250 h or 6 months, 500 h or 1 year, and 1000 h or 2 years.
Using it in design
- Pre-size the generator room discharge and inlet openings at 1.5 times the radiator area, then verify against the manufacturer's total air requirement table.
- Draw a sealed bellows connection between radiator and discharge opening and a layout (including a wind barrier) that stops hot air recirculating.
- Check 1 m service space around the set, outward-opening doors and an entry path wide enough to bring the set in and out.
- Give each set its own exhaust run, calculate back pressure against the manufacturer's limit and keep the outlet away from the clean-air inlet.
- Carry the plinth and vibration isolation into the structural design; use unevenly spaced, spring or rubber hangers for water, fuel and exhaust pipework.
Who should read it
Electrical and mechanical engineers designing generator rooms and standby power installations, site installers and operations staff.
Document contents
- Introduction
- Safety and Health
- General Definitions
- Storage, Lifting, Siting, Installation
- Periodic Maintenance
- Generator Operation and Panel
- Troubleshooting
- Quality Standards
- Warranty Terms and User Obligations
- Customer Services
Publication details
- Authors
- Alimar Jeneratör
- Publisher
- Alimar Jeneratör
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.
Citation
Alimar Jeneratör Alimar Jeneratör Kullanım Kılavuzu. Alimar Jeneratör. https://alimar.com.tr/litweb/wp-content/uploads/2023/09/Alimar-Manuel.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.