Immersed Computing: Asperitas Whitepaper
Original title Immersed Computing (Whitepaper)
Asperitas · Rolf Brink
A 2017 Asperitas whitepaper describing naturally circulating total liquid cooling: up to 22 kW of IT per unit for cloud and HPC, cooling with 40°C water, and a claimed 5-10 times the density of air-cooled racks.
On this page
Overview
The paper opens by arguing that the data-centre industry uses about 5% of global energy, that air cooling creates fan energy, vibration and zinc-whisker problems at high density, and that PUE rewards IT inefficiency. Liquid cooling is common in HPC but has stayed limited in cloud platforms because of complexity, cost and incompatibility, so a different approach, Immersed Computing, is proposed.
The approach rests on full immersion of electronics in dielectric oil, and suitable oils are said to absorb about 1,500 times more heat energy than air at the same volume and temperature. Asperitas chooses medicinal-grade oil; chemically engineered liquids usually cost 20 to 40 times more. The oil circulates without pumps: IT heat and water-cooled Convection Drives drive the flow, and a double hull with insulation sends all heat to the water circuit. In the example, 22 kW of IT becomes 22 kW of heat in water.
Benefits are set out under eight headings: fanless operation cutting IT energy by 10-45%, chiller-free operation with 40°C water, 5-10 times the density, no raised floors or aisle separation, smaller cooling and no-break power systems, fewer component failures, and fewer operating system and CPU licences. It is a vendor whitepaper; its numerical claims are not backed by independent measurement and commercial redistribution is prohibited.
Key points
- The industry is stated to consume about 5% of the global energy supply.
- In air-cooled servers, fans take 10-45% of total energy footprint; a 1U fan assembly reaches about 120 W.
- Suitable dielectric liquids absorb about 1,500 times more heat energy than air at the same volume and temperature.
- The system can be cooled with 40°C water, so chiller units are said to be unnecessary.
- An air-cooled rack carries about 5 kW of IT at 1.5-2 kW/m2; an immersed unit carries 22 kW in a 600x1200 mm footprint, above 15 kW/m2.
- Oil circulates without pumps or piping by thermal expansion and gravity; any common water infrastructure serves for heat rejection.
- Chemically engineered fluids usually cost 20-40 times more than medicinal-grade oil.
- One immersed server is argued to replace three or more low-power air-cooled servers.
Using it in design
- For an immersion design, size heat rejection on 40°C water and dry coolers; recalculate chiller need and free-cooling hours.
- Compare density on the same footprint basis, including rack service areas (600x2400/3600 mm for an air-cooled rack), so kW/m2 figures are like for like.
- Assess the effect of removing raised floors and aisle separation on floor loading and fluid management (double hull, oil filtering).
- Resize UPS and generator capacity for the reduced fan and cooling load, and note that PUE does not show the fan energy saving.
Who should read it
Planners and designers evaluating immersion cooling for cloud, HPC and edge data centres.
Document contents
- Background
- Immersed Computing explained (total liquid cooling, enclosed and self contained, flexibility, way of work)
- Benefits (energy efficiency, data-centre build, facilities, operations, IT hardware, software efficiency, environments with greatest benefits)
- Asperitas solutions
- Best practices (data-centre planning, liquid processes, IT and platform design)
- Asperitas company
Publication details
- Authors
- Rolf Brink
- Publisher
- Asperitas
- Year
- 2017
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
© Asperitas; copy distributed via eeNews Europe
Citation
Rolf Brink (2017). Immersed Computing (Whitepaper). Asperitas. https://www.eenewseurope.com/download_whitepaper/21910
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
