Water Quality in Hydronic Systems (Caleffi idronics 18)
Original title Water Quality in Hydronic Systems
Caleffi North America
Second edition of Caleffi North America's idronics 18 journal: hardness, dissolved gas, conductivity and pH management in hydronic loops, and a commissioning sequence of pressure test, flushing and demineralization.
On this page
Overview
The document is the second edition of issue 18 of Caleffi North America's technical journal idronics. The first edition reached about 80,000 people in North America; the second extends air and dirt separation to the quality of the water itself, especially demineralization of raw water. The aim is to reach water properties that let the hydronic circuit run efficiently, reliably and long.
The technical part lists the characteristics that determine water quality: turbidity, microbial corrosion, scaling (hardness salts, calcium phosphate and sulfate), dissolved minerals, conductivity and galvanic corrosion. Hardness is given in grains per gallon or ppm (1 gpg = 17.1 ppm). Untreated river, lake or well water typically has a TDS of 50-500 ppm, sea water up to 40,000 ppm.
The commissioning section gives a sequence: pressure test (air rather than water is recommended so no draining is needed to repair a leak), debris flushing and chemical cleaning, internal washing, final fill with demineralized water (once-through and recirculation methods), demineralized make-up, pH adjustment and film-forming treatment. The pH of demineralized water can initially fall to 5-6 and rises as gas is driven out while the system runs at design temperature.
The source is a general hydronic guide for building heating and cooling and gives no data-centre-specific limits; product examples belong to the manufacturer. It offers an ordered framework for setting up the first-fill and water-quality procedure of chilled-water and heat-rejection loops.
Key points
- Hardness conversion: 1 gpg = 17.1 ppm; the map shows hardness in five classes from under 60 ppm to over 250 ppm.
- Untreated river, lake or well water typically has a TDS of 50-500 ppm; sea water can reach 40,000 ppm.
- Pressure testing should use air; testing with water requires draining before soldered or welded repairs and brings freeze risk.
- The demineralizing unit produces water with 10-30 ppm TDS in a single pass; that residual ion content gives enough conductivity for low-water cutoff controls.
- The smaller fill unit delivers up to 6 gallons per minute, adequate to purge piping up to 1 inch.
- The pH of demineralized water can drop to 5-6; running the system at design temperature drives out dissolved CO2 and pH rises with time.
- Dissolved oxygen should be minimised by proper initial purging and air removal; high oxygen drives corrosion reactions.
- Commissioning order: pressure test, debris flushing and chemical cleaning, internal washing, final fill and demineralization, pH adjustment, film-forming treatment.
Using it in design
- Write pressure test, flushing, final fill and water-quality verification into the chilled-water and heat-rejection commissioning plan in that order.
- Define the water-quality target (TDS, conductivity, pH) for first fill and make-up; measure raw-water hardness and decide between demineralization and softening.
- Plan pressure testing with air where possible; if water is used, add freeze risk and draining time to the schedule.
- Place air and dirt separators along the circuit and include a step of bringing the loop to design temperature at first operation to remove dissolved gases.
- For circuits with conductivity-dependent controls such as low-water cutoff, check the residual conductivity of demineralized water.
Who should read it
Mechanical engineers and operations teams who design, commission and maintain the water quality of chilled-water and hydronic circuits.
Document contents
- Introduction
- Characteristics That Determine Water Quality (turbidity, microbial corrosion, scaling, dissolved minerals, conductivity, galvanic corrosion)
- Demineralizing Devices
- Commissioning Hydronic Systems for High Water Quality (pressure test, debris flushing and chemical cleaning, internal washing, final fill and demineralization, pH adjustment, film-forming treatment)
- Summary
Publication details
- Authors
- Caleffi North America
- Publisher
- Caleffi North America
- Year
- 2016
- Document number
- idronics 18
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public manufacturer source inspected. No redistribution permission established. Metadata and original brief summaries only; local files are research evidence, not a redistribution package.
Citation
Caleffi North America (2016). Water Quality in Hydronic Systems. Caleffi North America. idronics 18. https://www.caleffi.com/sites/default/files/media/file/idronics_18_na.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
