TANPERA TGB Series Shell and Tube Heat Exchanger User Manual
Original title TGB Serisi Gövde Borulu Eşanjör Kullanım Kılavuzu
Tanpera
The TANPERA TGB shell-and-tube heat exchanger manual describes construction, installation, start-up sequence and operating rules for AISI 300 stainless steel units in 10 pages.
On this page
Overview
The manual guides installation, commissioning and maintenance of all shell-and-tube heat exchangers made by TANPERA. It stresses that each exchanger is designed for the customer's stated pressure, temperature, capacity and fluid; changing design conditions needs the manufacturer's review and written approval, and the nameplate is then changed. Pressure surges during start-up or shut-down can seriously damage the exchanger.
The safety section requires the unit to be unpressurised and cooled below 40°C before work; gloves are advised against sharp edges and protective measures against burns. Flow must not start on the hot side before it starts on the cold side, or boiling can occur on the cold side. If freezing is possible the exchanger must be drained fully; for demountable types it recommends a drip tray underneath, a protective plate above 60°C or with aggressive fluids, and not using the exchanger for earthing during nearby welding.
The technical description says the units are built of AISI 300 series stainless steel and fitted as standard with corrugated inner tubes to improve heat transfer. Components are inner tubes, tube sheet, shell, nozzles, expansion bellows, baffles and gaskets. Mechanical design follows PED and ASME; each unit is sized with a thermal design programme, and multi-pass or multi-unit (series or parallel) configurations are possible. The nameplate shows maximum pressure and temperature, hydrostatic test pressure, corrosion allowance, volumes and dry weight.
The installation and operation section recommends an inlet strainer, isolation valves, no piping loads on the exchanger, flange bolts tightened crosswise in at least two steps and thermowells where instrumentation is used. At start-up vents are opened and cold fluid is introduced gradually first; on steam service condensate is drained. Shut-down reverses the order. Fixed-tubesheet exchangers must not be thermally shocked; cooling water should be monitored for quantity and quality (particles, pH) and water filters inspected regularly.
Key points
- The manual applies only to TANPERA shell-and-tube exchangers and runs to 10 pages.
- Unit material is AISI 300 series stainless steel; standard inner tubes are corrugated.
- Mechanical design follows PED and ASME.
- Before work the unit must be unpressurised and below 40°C.
- Do not start flow on the hot side before the cold side; boiling can occur on the cold side.
- If freezing is possible the exchanger must be drained completely.
- Above 60°C or with aggressive fluids a protective plate is advised, plus a drip tray underneath.
- Flange bolts are tightened crosswise in at least two steps; piping loads must not be carried by the exchanger.
- Nameplate pressure and temperature limits must never be exceeded.
Using it in design
- Put a strainer at the exchanger inlet and isolation valves on both circuits so it can be isolated for maintenance.
- Write the start-up and shut-down procedure with cold fluid first in, hot fluid first out and venting.
- Support piping independently of the exchanger and consider expansion elements for thermal growth.
- If design conditions (flow, temperature, fluid) change, have the manufacturer re-evaluate; treat nameplate values as acceptance limits.
- Fit a filter on the cooling water line and add particle and pH monitoring to the maintenance plan.
Who should read it
Mechanical designers and site engineers responsible for installing, commissioning and maintaining shell-and-tube exchangers.
Document contents
- Foreword
- Introduction
- Safety warnings
- General (product identification, correct operation, warnings)
- Thermal design
- Technical description of heat exchangers
- Installation
- Start-up procedure
- Operating procedures
Publication details
- Authors
- Tanpera
- Publisher
- Tanpera
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official publisher material inspected. No document-specific commercial redistribution permission established; retain metadata and original short summaries only.
Citation
Tanpera TGB Serisi Gövde Borulu Eşanjör Kullanım Kılavuzu. Tanpera. https://www.tanpera.com.tr/content/wp-import/2025/05/Borulu_Esanjorler_Kullanim_Klavuzu_TR_V0.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.