Technical guideFree to read2022

3,000 ekW, 60 Hz Generator Set: Diesel & HVO Test

Caterpillar · Caterpillar Inc.

Caterpillar LEXE20432-02 (2022) reports back-to-back test-cell runs of a Cat 3516E 3,000 ekW, 60 Hz data-centre-class generator set on conventional diesel and neat HVO (R100). It concludes HVO is a viable drop-in fuel with minor trade-offs.

On this page

Overview

The comparison covers steady-state performance, fuel use, NOx and smoke, ISO 8528-5 and SpecSizer transient tests, and NFPA 110 start tests. At equal fuel delivery the engine produced 3.6% less power on HVO, although most 3500 Series engines are expected to derate by under 2% once fuelling rises to its limit. Transient tests showed on average 1.3% greater frequency droop with HVO.

Frequency dip crossed the G3 limit at about 41% block load on HVO against 43% on diesel, and the G2 limit at about 48% against 51% (2:1 V/Hz, PF 1.0). Both fuels reached 1800 rpm steady speed in under 7 s with jacket water at 60 C, meeting NFPA 110 Type 10.

On emissions, smoke opacity with HVO was about half that of diesel, with FSN up to about 60% lower down to roughly 28% load. NOx was not significantly different at high load but up to about 40% lower at 50% load and below. Cat judged 3500 fuel-system seals and hoses compatible with HVO and all HVO-diesel blends.

Key points

  1. At equal fuel delivery HVO gave 3.6% less power; most 3500 engines expected to derate under 2% at the fuel limit.
  2. Transient tests showed on average 1.3% greater frequency droop on HVO.
  3. G3 limit crossed at about 41% block load on HVO vs 43% on diesel; G2 at about 48% vs 51%.
  4. Both fuels reached 1800 rpm in under 7 s and met NFPA 110 Type 10.
  5. HVO smoke opacity about 50% of diesel; FSN up to about 60% lower down to about 28% load.
  6. NOx similar at high load, up to about 40% lower at 50% load or less.
  7. 3500 fuel-system seals and hoses compatible with HVO and all blends.

Using it in design

  • Store a fuel compatibility list (diesel, HVO/EN 15940) with an HVO derate percentage and an HVO-specific maximum block-load step in the catalog.
  • When project fuel is HVO, apply about a 2% kW derate and cut the allowable first load step by a few points versus diesel figures.
  • Keep the NFPA 110 Type 10 start check for HVO.
  • Assess HVO as a separate fuel scenario in Scope 1 emissions reporting.

Who should read it

Electrical designers and operators evaluating HVO for data-centre generators.

Related standards

  • ISO 8528-5
  • NFPA 110
  • EN 15940

Publication details

Authors
Caterpillar Inc.
Publisher
Caterpillar
Year
2022
Document number
LEXE20432-02
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Caterpillar Inc. (2022). 3,000 ekW, 60 Hz Generator Set: Diesel & HVO Test. Caterpillar. LEXE20432-02. https://www.finning.com/content/dam/finning/en_gb/Documents/Industries/ElectricPower/cat-white-papers-march-2024/3,000%20ekW,%2060%20Hz%20Generator%20Set%20Diesel%20And%20HVO%20Test%20(LEXE20432-02).pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.