CONTEG CoolDoor in-rack cooling units datasheet
Original title CONTEG cooldoor datasheet, current download accessed 2026-11-16
CONTEG
CONTEG CoolDoor is a chilled-water rear-door rack cooling module rated up to 85 kW at 20 °C water inlet and 24 °C air supply, in 600/800 mm widths and 42U to 52U heights.
On this page
Overview
The datasheet presents CONTEG's CoolDoor family: compact rear-door modules that connect to any chilled-water system. The maker says they perform well with high return-water temperature, which extends free-cooling hours and lowers running cost. Modules come in 600 and 800 mm widths and 42U, 47U and 52U heights.
The table gives two capacity classes: 60 kW for 42U/47U (height 2050 mm, 5 fans) and 85 kW for 52U (height 2330 mm, 6 fans). Rated capacity assumes 20 °C supply water, 30 °C return water and 24 °C supply air; depth is 380 mm. Fan speed is tabulated from 25 to 100%: for 42U/47U air flow is 2125-8500 m3/h, power 39-844 W and noise 62-85 dB; for 52U 2550-10200 m3/h, 47-1013 W and 63-86 dB.
Reliability and service features include tool-free hot-swappable EC fans, N+1 fan redundancy, dual power feed with an automatic transfer switch (ATS), a standard leak sensor that shuts the water supply, flexible hoses isolated from IT equipment and a controller serviceable with the door closed. Supply is 230 V single phase 50-60 Hz, dry weight 152-186 kg, pipe connection 25 mm (1 inch), communication Modbus TCP (BACnet optional), operating temperature 5-50 °C and maximum altitude 2000 m.
Key points
- Total cooling capacity 60 kW (42U/47U) and 85 kW (52U); 20/30 °C water, 24 °C supply air.
- Width 600/800 mm, depth 380 mm, height 2050 mm (42U/47U) or 2330 mm (52U).
- Air flow at 100% speed 8500 m3/h (5 fans) and 10200 m3/h (6 fans).
- Fan power at 100% speed 844 W and 1013 W; noise 85 and 86 dB.
- Hot-swap EC fans, N+1 fan redundancy, dual feed with ATS, leak sensor with automatic water shut-off.
- Dry weight 152-186 kg, wet weight 165-204 kg; 1 inch pipe connection.
- Modbus TCP standard, BACnet optional; 5-50 °C operation, 2000 m altitude limit.
Using it in design
- Compare the heat load per rack with the 60 or 85 kW limit and verify the water temperature (20/30 °C) against the rating condition.
- Design chiller and dry-cooler plant around the high return-water regime to increase free-cooling hours.
- Show weight, 1 inch pipe connections and leak management (automatic shut-off valve) in the rack layout and piping drawings.
- Carry the dual feed and ATS into A/B power distribution and Modbus/BACnet points into BMS integration.
- Add the infill panel required for 47U and 52U cabinets to the cabinet specification.
Who should read it
Mechanical engineers designing high-density rack cooling and data-centre operators.
Document contents
- Main advantages
- Technical table (capacity, dimensions, fan performance)
- Basic data
- Piping connection
- Accessories
Publication details
- Authors
- CONTEG
- Publisher
- CONTEG
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
CONTEG CONTEG cooldoor datasheet, current download accessed 2026-11-16. CONTEG. https://www.conteg.com/userfiles/cooldoor-datasheet-conteg-en-ac84fe1c.pdf?v=
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.