CONTEG CoolDoor in-rack cooling units datasheet

Original title CONTEG cooldoor datasheet, current download accessed 2026-11-16

CONTEG

CONTEG CoolDoor is a chilled-water rear-door rack cooling module rated up to 85 kW at 20 °C water inlet and 24 °C air supply, in 600/800 mm widths and 42U to 52U heights.

On this page

Overview

The datasheet presents CONTEG's CoolDoor family: compact rear-door modules that connect to any chilled-water system. The maker says they perform well with high return-water temperature, which extends free-cooling hours and lowers running cost. Modules come in 600 and 800 mm widths and 42U, 47U and 52U heights.

The table gives two capacity classes: 60 kW for 42U/47U (height 2050 mm, 5 fans) and 85 kW for 52U (height 2330 mm, 6 fans). Rated capacity assumes 20 °C supply water, 30 °C return water and 24 °C supply air; depth is 380 mm. Fan speed is tabulated from 25 to 100%: for 42U/47U air flow is 2125-8500 m3/h, power 39-844 W and noise 62-85 dB; for 52U 2550-10200 m3/h, 47-1013 W and 63-86 dB.

Reliability and service features include tool-free hot-swappable EC fans, N+1 fan redundancy, dual power feed with an automatic transfer switch (ATS), a standard leak sensor that shuts the water supply, flexible hoses isolated from IT equipment and a controller serviceable with the door closed. Supply is 230 V single phase 50-60 Hz, dry weight 152-186 kg, pipe connection 25 mm (1 inch), communication Modbus TCP (BACnet optional), operating temperature 5-50 °C and maximum altitude 2000 m.

Key points

  1. Total cooling capacity 60 kW (42U/47U) and 85 kW (52U); 20/30 °C water, 24 °C supply air.
  2. Width 600/800 mm, depth 380 mm, height 2050 mm (42U/47U) or 2330 mm (52U).
  3. Air flow at 100% speed 8500 m3/h (5 fans) and 10200 m3/h (6 fans).
  4. Fan power at 100% speed 844 W and 1013 W; noise 85 and 86 dB.
  5. Hot-swap EC fans, N+1 fan redundancy, dual feed with ATS, leak sensor with automatic water shut-off.
  6. Dry weight 152-186 kg, wet weight 165-204 kg; 1 inch pipe connection.
  7. Modbus TCP standard, BACnet optional; 5-50 °C operation, 2000 m altitude limit.

Using it in design

  • Compare the heat load per rack with the 60 or 85 kW limit and verify the water temperature (20/30 °C) against the rating condition.
  • Design chiller and dry-cooler plant around the high return-water regime to increase free-cooling hours.
  • Show weight, 1 inch pipe connections and leak management (automatic shut-off valve) in the rack layout and piping drawings.
  • Carry the dual feed and ATS into A/B power distribution and Modbus/BACnet points into BMS integration.
  • Add the infill panel required for 47U and 52U cabinets to the cabinet specification.

Who should read it

Mechanical engineers designing high-density rack cooling and data-centre operators.

Document contents

  1. Main advantages
  2. Technical table (capacity, dimensions, fan performance)
  3. Basic data
  4. Piping connection
  5. Accessories

Publication details

Authors
CONTEG
Publisher
CONTEG
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

CONTEG CONTEG cooldoor datasheet, current download accessed 2026-11-16. CONTEG. https://www.conteg.com/userfiles/cooldoor-datasheet-conteg-en-ac84fe1c.pdf?v=

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.