CONTEG CoolRAC CW chilled water room cooling units datasheet

Original title CONTEG coolrac cw datasheet, current download accessed 2026-11-16

CONTEG

CONTEG CoolRAC CW is a chilled-water precision cooling family with EC fans, 45 to 101.8 kW net capacity and up to 104.3 kW nominal at 35 °C return air and 6/12 °C water.

On this page

Overview

The datasheet introduces the CoolRAC room cooling family and its chilled-water (CW) member. The family has three systems: CW (chilled water), XC (direct expansion with compressor) and DF (dual-fluid hybrid). Units suit open aisles and contained cold/hot aisles, from small server rooms to large data centres; the fan module and air outlet can sit in the raised floor or above it.

The CW table gives four models: net capacity 45, 57.6, 84.6 and 101.8 kW (nominal 46.5, 59, 87.1 and 104.3 kW). Nominal capacity is for 35 °C return air without condensation, 6/12 °C water and clean filters; net capacity is after fan heat. Water flow is 6640-17990 l/h, air flow 10300-16026 m3/h, supply 400 V 3-phase, maximum fan power 1.4 kW (small) and 2.5 kW (medium), filter class G4.

The small casing is 714 x 2025 x 763 mm and 200-210 kg, the medium 1353 x 2025 x 763 mm and 290-295 kg; pipe connections are 5/4 inch and 6/4 inch female. The controller has a 4.3 inch touch screen and group control of up to 16 units; TCP/IP is standard, Modbus and SNMP cards optional. The sheet also defines the 16-position order code and options for humidifier, condensate pump, dual power supply and electric reheat (600-1200 W).

Key points

  1. Net capacity 45, 57.6, 84.6, 101.8 kW (nominal 46.5, 59, 87.1, 104.3 kW).
  2. Nominal condition: 35 °C return air, 6/12 °C water, clean filters; net value excludes fan heat.
  3. Water flow 6640-17990 l/h; air flow 10300-16026 m3/h.
  4. EC fans, 400 V 3-phase; maximum fan power 1.4 kW (S) and 2.5 kW (M).
  5. Casing 714 or 1353 mm wide, 2025 mm high; weight 200-295 kg.
  6. Pipe connection 5/4 inch (S) and 6/4 inch (M) female.
  7. One display manages 16 units; TCP/IP standard, Modbus and SNMP optional; raised-floor and above-floor installation.

Using it in design

  • Select on net capacity; include the fan-heat difference between nominal and net in the load calculation.
  • If a water temperature warmer than 6/12 °C is planned, have the coil capacity recalculated by the manufacturer.
  • Sum unit water flows to check main pipe size, pump and chiller selection.
  • Medium-casing depth is 763 mm in the table and 790 mm in the order matrix; use the larger in layout.
  • Choose the in-floor fan module and air outlet option to match floor height and cold-aisle concept.

Who should read it

Mechanical designers selecting chilled-water precision cooling and data-hall planners.

Document contents

  1. CoolRAC room cooling system
  2. Description and three cooling systems
  3. CoolRAC CW technical table
  4. Order code
  5. Basic accessories

Publication details

Authors
CONTEG
Publisher
CONTEG
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

CONTEG CONTEG coolrac cw datasheet, current download accessed 2026-11-16. CONTEG. https://www.conteg.com/userfiles/coolrac-cw-datasheet-conteg-en-4b866751.pdf?v=g9p1gxncqc

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.