CONTEG CoolRAC CW chilled water room cooling units datasheet
Original title CONTEG coolrac cw datasheet, current download accessed 2026-11-16
CONTEG
CONTEG CoolRAC CW is a chilled-water precision cooling family with EC fans, 45 to 101.8 kW net capacity and up to 104.3 kW nominal at 35 °C return air and 6/12 °C water.
On this page
Overview
The datasheet introduces the CoolRAC room cooling family and its chilled-water (CW) member. The family has three systems: CW (chilled water), XC (direct expansion with compressor) and DF (dual-fluid hybrid). Units suit open aisles and contained cold/hot aisles, from small server rooms to large data centres; the fan module and air outlet can sit in the raised floor or above it.
The CW table gives four models: net capacity 45, 57.6, 84.6 and 101.8 kW (nominal 46.5, 59, 87.1 and 104.3 kW). Nominal capacity is for 35 °C return air without condensation, 6/12 °C water and clean filters; net capacity is after fan heat. Water flow is 6640-17990 l/h, air flow 10300-16026 m3/h, supply 400 V 3-phase, maximum fan power 1.4 kW (small) and 2.5 kW (medium), filter class G4.
The small casing is 714 x 2025 x 763 mm and 200-210 kg, the medium 1353 x 2025 x 763 mm and 290-295 kg; pipe connections are 5/4 inch and 6/4 inch female. The controller has a 4.3 inch touch screen and group control of up to 16 units; TCP/IP is standard, Modbus and SNMP cards optional. The sheet also defines the 16-position order code and options for humidifier, condensate pump, dual power supply and electric reheat (600-1200 W).
Key points
- Net capacity 45, 57.6, 84.6, 101.8 kW (nominal 46.5, 59, 87.1, 104.3 kW).
- Nominal condition: 35 °C return air, 6/12 °C water, clean filters; net value excludes fan heat.
- Water flow 6640-17990 l/h; air flow 10300-16026 m3/h.
- EC fans, 400 V 3-phase; maximum fan power 1.4 kW (S) and 2.5 kW (M).
- Casing 714 or 1353 mm wide, 2025 mm high; weight 200-295 kg.
- Pipe connection 5/4 inch (S) and 6/4 inch (M) female.
- One display manages 16 units; TCP/IP standard, Modbus and SNMP optional; raised-floor and above-floor installation.
Using it in design
- Select on net capacity; include the fan-heat difference between nominal and net in the load calculation.
- If a water temperature warmer than 6/12 °C is planned, have the coil capacity recalculated by the manufacturer.
- Sum unit water flows to check main pipe size, pump and chiller selection.
- Medium-casing depth is 763 mm in the table and 790 mm in the order matrix; use the larger in layout.
- Choose the in-floor fan module and air outlet option to match floor height and cold-aisle concept.
Who should read it
Mechanical designers selecting chilled-water precision cooling and data-hall planners.
Document contents
- CoolRAC room cooling system
- Description and three cooling systems
- CoolRAC CW technical table
- Order code
- Basic accessories
Publication details
- Authors
- CONTEG
- Publisher
- CONTEG
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
CONTEG CONTEG coolrac cw datasheet, current download accessed 2026-11-16. CONTEG. https://www.conteg.com/userfiles/coolrac-cw-datasheet-conteg-en-4b866751.pdf?v=g9p1gxncqc
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.