CONTEG CoolRAC DF dual-fluid hybrid room cooling units datasheet
Original title CONTEG coolrac df datasheet, current download accessed 2026-11-16
CONTEG
CONTEG CoolRAC DF is a dual-fluid hybrid precision unit that combines free-cooling and direct expansion in one cabinet, up to 45.8 kW, with R410A and an inverter compressor.
On this page
Overview
The datasheet presents CoolRAC DF as combining the advantages of CW and XC systems: water free-cooling at low and medium outdoor temperatures and direct expansion at high outdoor temperatures. The water circuit and compressor circuit can connect to two separate water sources. The maker says the unit can run in free-cooling for much of the year; in an example calculated with Prague climate data this share is about 60%.
The table lists two models: 25 kW (net 23.6) and 45.8 kW (net 45.1; 44.5 on the compressor circuit). Conditions are outlet-air parameters of 35 °C at 30% RH, 45 °C condensing temperature, 11/20 °C water and no glycol. For the larger model running current is 18.1 A, maximum current 25.9 A, fan power 0.7 kW, compressor power 11.2 kW, maximum air flow 12320 m3/h, water flow 4.3 m3/h and pressure loss 40 kPa.
The small model is 714 mm wide and the large 1353 mm; height 2025 mm, depth 763 mm; weights 300 and 376 kg, refrigerant R410A (3 kg charge). The operating range is -40 to +40 °C with the upper limit depending on size. The smart control uses free-cooling to pre-cool air even at high outdoor temperature. The order code defines humidifier, heater and communication card options.
Key points
- Nominal capacity 25 kW (net 23.6) and 45.8 kW (net 45.1).
- Free-cooling and compressor modes; in a Prague example about 60% of the year is free-cooling.
- Operating range -40 to +40 °C; inverter compressor, R410A.
- Large model: maximum current 25.9 A, compressor 11.2 kW, fan 0.7 kW.
- Water circuit and compressor circuit may connect to two separate water sources.
- Casing 714 or 1353 x 2025 x 763 mm; weight 300 and 376 kg.
- Nominal condition: 35 °C/30% RH, 45 °C condensing, 11/20 °C water.
Using it in design
- Recalculate the free-cooling share with project climate data; the Prague example does not transfer to another city.
- Do not add water capacity and compressor capacity; they are alternative operating modes.
- Connect the water circuit to a high-temperature dry-cooler loop and the compressor circuit to a separate source to build redundancy.
- Carry running and maximum current into panel and UPS sizing; mind the starting current of a compressor unit.
Who should read it
Mechanical designers combining free-cooling with precision air conditioning, and data-centre energy-efficiency planners.
Document contents
- Main advantages
- Annual split of free-cooling and compressor mode
- Technical table
- Order code
- Accessories
Publication details
- Authors
- CONTEG
- Publisher
- CONTEG
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
CONTEG CONTEG coolrac df datasheet, current download accessed 2026-11-16. CONTEG. https://www.conteg.com/userfiles/coolrac-df-datasheet-conteg-en-d0de740c.pdf?v=zmwmwskpsr
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.