CONTEG CoolRAC XC direct expansion room cooling units with integrated compressor datasheet

Original title CONTEG coolrac xc datasheet, current download accessed 2026-11-16

CONTEG

CONTEG CoolRAC XC is a direct-expansion precision unit with the compressor in the indoor cabinet, rated 24.7 and 45.8 kW nominal on R410A, with outdoor range of -40 to +55 °C.

On this page

Overview

The datasheet presents the XC member of the CoolRAC family: the compressor sits inside the data centre in the indoor unit and only the condenser is outdoors. The maker highlights capacity up to 46 kW, an operating range of -40 to +55 °C, stepless capacity control and R410A refrigerant.

The technical table has two models: 24.7 kW (net 23.3) and 45.8 kW (net 45.2). The condition is inlet air at 35 °C and 30% RH with 45 °C condensing temperature. The small model has running current 13.5 A, maximum current 21 A, fan 1.4 kW, compressor 7.2 kW and nominal air flow 5000 m3/h; the large model 18.1 A, 25.9 A, 1.3 kW, 11.7 kW and 10300 m3/h. Casing is 714 or 1353 x 2025 x 763 mm, weight 290 and 330 kg, liquid line 12 and 16 mm.

The outdoor condenser table offers three options by maximum ambient: AC-COND2-03-35 for 35 °C (87 dB Lw, 56 dB Lp at 10 m, 4.2 A, 2.59 kW, 158 kg), AC-COND2-02-45 for 45 °C (93/61 dB, 6.2 A, 4.02 kW, 236 kg) and AC-COND2-03-55 for 55 °C (96/64 dB, 8.6 A, 5.77 kW, 267 kg). All three have two fans and 400 V 3-phase supply. Control and order code are shared with the other CoolRAC members.

Key points

  1. Nominal capacity 24.7 kW (net 23.3) and 45.8 kW (net 45.2).
  2. Nominal condition: 35 °C/30% RH inlet air, 45 °C condensing.
  3. Compressor power 7.2 and 11.7 kW; fan power 1.4 and 1.3 kW.
  4. Operating range -40 to +55 °C; stepless capacity control, R410A.
  5. Air flow nominal 5000 and 10300 m3/h, maximum 10400 and 13040 m3/h.
  6. Casing 714/1353 x 2025 x 763 mm; weight 290 and 330 kg; liquid line 12 and 16 mm.
  7. Outdoor condenser: 35/45/55 °C options, 158-267 kg, sound power 87-96 dB(A).

Using it in design

  • Select the outdoor condenser for the site maximum ambient (35, 45 or 55 °C) and compare sound pressure (56-64 dB(A) at 10 m) with the environmental limit.
  • Read capacity separately from fan and compressor power; use the currents for electrical load.
  • Check refrigerant pipe length and liquid-line size (12/16 mm) in the indoor-to-condenser layout.
  • Because the compressor unit needs no water, consider it for rooms without a chiller plant.

Who should read it

Mechanical designers selecting direct-expansion precision cooling and planners of small and medium data halls.

Document contents

  1. Main advantages
  2. CoolRAC XC technical table
  3. Outdoor condenser table
  4. Order code
  5. Accessories

Publication details

Authors
CONTEG
Publisher
CONTEG
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

CONTEG CONTEG coolrac xc datasheet, current download accessed 2026-11-16. CONTEG. https://www.conteg.com/userfiles/coolrac-xc-datasheet-conteg-en-20345060.pdf?v=gwurimc7na

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.